5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
Function:
Reference site
set in
3-13 Reference
Site
Local
referen
ce
active
[120]
Remote
reference
active
[121]
Reference site:
Local
3-13 Reference
Site
[2]
1
0
Reference site:
Remote
3-13 Reference
Site
[1]
0
1
Reference site:
Linked to
Hand/ Auto
Hand
1
0
Hand -> off
1
0
Auto -> off
0
0
Auto
0
1
Table 3.18
[121] Remote ref active
Output is high when
3-13 Reference
Site
= Remote [1] or Linked to hand/
auto [0] while the LCP is in [Auto on]
mode. See above.
[122] No alarm
Output is high when no alarm is
present.
[123] Start command
activ
Output is high when the Start
command high (i.e. via digital input,
bus connection or [Hand On] or
[Auto On] ), and a Stop has been last
command.
[124] Running reverse
Output is high when the frequency
converter is running counter
clockwise (the logical product of the
status bits ‘running’ AND ‘reverse’).
[125] Drive in hand mode Output is high when the frequency
converter is in [Hand on] mode (as
indicated by the LED light above
[Hand on]).
[126] Drive in auto mode
Output is high when the frequency
converter is in ‘Auto’ mode (as
indicated by LED on above [Auto
on] ).
[151] ATEX ETR cur. alarm Selectable if
is set to [20] or [21]. If the
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
Function:
alarm 164 ATEX ETR cur.lim.alarm is
active, the output will be 1.
[152] ATEX ETR freq.
alarm
Selectable if
is set to [20] or [21]. If the
alarm 166 ATEX ETR freq.lim.alarm is
active, the output will be 1.
[153] ATEX ETR cur.
warning
Selectable if
is set to [20] or [21] ]. If
the alarm 163 ATEX ETR
cur.lim.warning is active, the output
will be 1.
[154] ATEX ETR freq.
warning
Selectable if
is set to [20] or [21]. If the
warning 165 ATEX ETR
freq.lim.warning is active, the output
will be 1.
[188] AHF Capacitor
Connect
[189] External Fan Control The internal logics for the internal
fan control is transferred to this
output to make it possible to control
an external fan (relevant for HP duct
cooling).
[192] RS Flipflop 0
[193] RS Flipflop 1
[194] RS Flipflop 2
[195] RS Flipflop 3
[196] RS Flipflop 4
[197] RS Flipflop 5
[198] RS Flipflop 6
[199] RS Flipflop 7
5-41 On Delay, Relay
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
*
[0.01 - 600.00 s] Enter the delay of the relay cut-in
time. Select one of available
mechanical relays and MCB 105 in an
array function. See
5-40 Function Relay
.
Relay 3-6 are included in MCB 113.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
84
MG33ME02 - VLT
®
is a registered Danfoss trademark