6 Application Set-up Examples
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
parameter 0-03 Regional Settings
).
•
Parameters associated with the terminals and
their settings are shown next to the drawings.
•
Required switch settings for analog terminals A53
or A54 are also shown.
NOTICE
When using the optional STO feature, a jumper wire may
be required between terminal 12 (or 13) and terminal 37
for the frequency converter to operate with factory
default programming values.
6.1 Application Examples
6.1.1 AMA
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB929.10
Function
Setting
Parameter 1-29 A
utomatic Motor
Adaptation
(AMA)
[1] Enable
complete
AMA
Parameter 5-12 T
erminal 27
Digital Input
[2] Coast
inverse
Notes/comments:
Set parameter group
1-2* Motor
Data
according to the motor.
D IN 37 is an option.
Table 6.1 AMA with T27 Connected
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB930.10
Function
Setting
Parameter 1-29 A
utomatic Motor
Adaptation
(AMA)
[1] Enable
complete
AMA
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
Notes/comments:
Set parameter group
1-2* Motor
Data
according to the motor.
D IN 37 is an option.
Table 6.2 AMA without T27 Connected
6.1.2 Speed
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
-10 - +10V
+
-
130BB926.10
Function
Setting
Parameter 6-10 T
erminal 53 Low
Voltage
0.07 V*
Parameter 6-11 T
erminal 53 High
Voltage
10 V*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 Hz
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
50 Hz
* = Default value
Notes/comments:
D IN 37 is an option.
Table 6.3 Analog Speed Reference (Voltage)
Application Set-up Examples
Operating Instructions
MG33AQ02
Danfoss A/S © 07/2015 All rights reserved.
31
6
6
Summary of Contents for VLT AutomationDrive FC 301