8.1.2 Mains Supply 380–500 V
Type designation
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
Typical shaft output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3.0
4.0
5.5
7.5
Enclosure protection rating IP20 (FC 301 only)
A1
A1
A1
A1
A1
–
–
–
–
–
Enclosure protection rating IP20/IP21
A2
A2
A2
A2
A2
A2
A2
A2
A3
A3
Enclosure protection rating IP55, IP66
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current high overload 160% for 1 minute
Shaft output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Continuous (380–440 V) [A]
1.3
1.8
2.4
3.0
4.1
5.6
7.2
10
13
16
Intermittent (380–440 V) [A]
2.1
2.9
3.8
4.8
6.6
9.0
11.5
16
20.8
25.6
Continuous (441–500 V) [A]
1.2
1.6
2.1
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent (441–500 V) [A]
1.9
2.6
3.4
4.3
5.4
7.7
10.1
13.1
17.6
23.2
Continuous kVA (400 V) [kVA]
0.9
1.3
1.7
2.1
2.8
3.9
5.0
6.9
9.0
11
Continuous kVA (460 V) [kVA]
0.9
1.3
1.7
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Maximum input current
Continuous (380–440 V) [A]
1.2
1.6
2.2
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent (380–440 V) [A]
1.9
2.6
3.5
4.3
5.9
8.0
10.4
14.4
18.7
23
Continuous (441–500 V) [A]
1.0
1.4
1.9
2.7
3.1
4.3
5.7
7.4
9.9
13
Intermittent (441–500 V) [A]
1.6
2.2
3.0
4.3
5.0
6.9
9.1
11.8
15.8
20.8
Additional specifications
IP20, IP21 maximum cable cross-section
2)
for
mains, motor, brake, and load sharing [mm
2
]
([AWG])
4,4,4 (12,12,12)
(minimum 0.2(24))
IP55, IP66 maximum cable cross-section
2)
for
mains, motor, brake, and load sharing [mm
2
]
([AWG])
4,4,4 (12,12,12)
Maximum cable cross-section
2)
for disconnect
[mm
2
] ([AWG])
6,4,4 (10,12,12)
Estimated power loss at rated maximum load
[W
3)
35
42
46
58
62
88
116
124
187
255
Efficiency
4)
0.93
0.95
0.96
0.96
0.97
0.97
0.97
0.97
0.97
0.97
Table 8.4 Mains Supply 380–500 V (FC 302), 380–480 V (FC 301), PK37–P7K5
Specifications
VLT
®
AutomationDrive FC 301/302
52
Danfoss A/S © 07/2015 All rights reserved.
MG33AQ02
8
8
Summary of Contents for VLT AutomationDrive FC 301
Page 2: ......