3.5.14 Mains Disconnectors - Frame Size D, E and F
Frame size
Power
Type
380-500 V
D1/D3
P90K-P110
ABB OT200U12-91
D2/D4
P132-P200
ABB OT400U12-91
E1/E2
P250
ABB OT600U03
E1/E2
P315-P400
ABB OT800U03
F3
P450
Merlin Gerin NPJF36000S12AAYP
F3
P500-P630
Merlin Gerin NRKF36000S20AAYP
F4
P710-P800
Merlin Gerin NRKF36000S20AAYP
525-690 V
D1/D3
P90K-P132
ABB OT200U12-91
D2/D4
P160-P315
ABB OT400U12-91
E1/E2
P355-P560
ABB OETL-NF600A
F3
P630-P710
Merlin Gerin NPJF36000S12AAYP
F3
P800
Merlin Gerin NRKF36000S20AAYP
F4
P900-P1M2
Merlin Gerin NRKF36000S20AAYP
Table 3.47 Mains Disconnector Types
3.5.15 F-Frame Circuit Breakers
Frame
size
Power & voltage
Type
Default breaker settings
Trip level [A]
Time [s]
F3
P450 380-500 V & P630-P710
525-690 V
Merlin Gerin
NPJF36120U31AABSCYP
1200
0.5
F3
P500-P630 380-500 V & P800
525-690 V
Merlin Gerin
NRJF36200U31AABSCYP
2000
0.5
F4
P710 380-500 V & P900-P1M2
525-690 V
Merlin Gerin
NRJF36200U31AABSCYP
2000
0.5
F4
P800 380-500 V
Merlin Gerin
NRJF36250U31AABSCYP
2500
0.5
Table 3.48 Circuit Breakers Types
3.5.16 F-Frame Mains Contactors
Frame size
Power & voltage
Type
F3
P450-P500 380-500 V & P630-P800 525-690 V
Eaton XTCE650N22A
F3
P560 380-500 V
Eaton XTCE820N22A
F3
P630380-500 V
Eaton XTCEC14P22B
F4
P900 525-690 V
Eaton XTCE820N22A
F4
P710-P800 380-500 V & P1M2 525-690 V
Eaton XTCEC14P22B
Table 3.49 Mains Contactor Types