130BA150.10
9 - 10 mm
(0.37 in)
Figure 4.9 Length to Strip the Insulation
2.
Insert a screwdriver (max. 0.016x0.1 in [0.4x2.5
mm]) in the square hole.
3.
Insert the cable in the adjacent circular hole.
130B
T312.10
Figure 4.10 Inserting the Cable in the Terminal Block
4.
Remove the screwdriver. The cable is now
mounted in the terminal.
To remove the cable from the terminal:
1.
Insert a screwdriver (max. 0.016x0.1 in [0.4x2.5
mm]) in the square hole.
2.
Pull out the cable.
130B
T311.10
Figure 4.11 Removing the Screwdriver after Cable Insertion
130B
T306.10
Figure 4.12 Control Terminal Locations
Electrical Installation
VLT
®
AutomationDrive FC 302 Low Harmonic Drive
132–630 kW
44
Danfoss A/S © Rev. 04/2015 All rights reserved.
MG37A322
4