P250
P315
P355
P400
Normal Overload =110% current for 60 s
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
250
315
315
355
355
400
400
450
Typical shaft output at 460 V [hp]
350
450
450
500
500
600
550
600
Typical shaft output at 480 V [kW]
315
355
355
400
400
500
500
530
Enclosure IP21/54
E9
Output current
Continuous (at 400 V) [A]
480
600
600
658
658
745
695
800
Intermittent (60 s overload) (at 400 V) [A]
720
660
900
724
987
820
1043
880
Continuous (at 460/480 V) [A]
443
540
540
590
590
678
678
730
Intermittent (60 s overload) (at 460/480 V)
[A]
665
594
810
649
885
746
1017
803
Continuous kVA (at 400 V) [kVA]
333
416
416
456
456
516
482
554
Continuous kVA (at 460 V) [kVA]
353
430
430
470
470
540
540
582
Continuous kVA (at 480 V) [kVA]
384
468
468
511
511
587
587
632
Max. Input current
Continuous (at 400 V) [A]
472
590
590
647
647
733
684
787
Continuous (at 460/480 V) [A]
436
531
531
580
580
667
667
718
Max. pre-fuses
1)
[A]
700
900
Max. cable size
Motor (mm
2
/AWG
2)
)
4x240 (4x500 mcm)
Line power (mm
2
/AWG
2
)
Load sharing (mm
2
/AWG
2)
)
Brake (mm
2
/AWG
2)
)
2x185 (2x350 mcm)
Total LHD loss 400 V AC [kW]
11587
14051
14140
15320
15286
17180
16036
18447
Total backchannel loss 400 V AC [kW]
9011
11301
10563
11648
11650
13396
12348
14570
Total filter loss 400 V AC [kW]
6528
7346
7346
7788
7788
8503
8060
8974
Total LHD loss 460 V AC [kW]
10962
12936
13124
14083
13998
15852
15847
16962
Total backchannel loss 460 V AC [kW]
8432
10277
9636
10522
10466
12184
12186
13214
Total filter loss 460 V AC [kW]
6316
7066
7006
7359
7326
8033
8033
8435
Weight, enclosure IP21, IP54 (lbs [kg])
1314 [596]
1374 [623]
1425 [646]
Efficiency
4)
0.96
Output frequency [Hz]
0–600
Heatsink overtemp. trip (°F [°C])
221 [105]
Power card ambient trip (°F [°C])
85
*High overload = 160% torque during 60 s; Normal overload = 110% torque during 60 s
Table 8.2 Line Power Supply 3x380–480 V AC
Specifications
Installation Manual
MG37A322
Danfoss A/S © Rev. 04/2015 All rights reserved.
87
8
8