P450
P500
P560
P630
Normal Overload =110% current
for 60 s
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
450
500
500
560
560
630
630
710
Typical shaft output at 460 V [hp]
600
650
650
750
750
900
900
1000
Typical shaft output at 480 V [kW]
530
560
560
630
630
710
710
800
Enclosure IP21/54
F18
Output current
Continuous (at 400 V) [A]
800
880
880
990
990
1120
1120
1260
Intermittent (60 s overload)
(at 400 V) [A]
1200
968
1320
1089
1485
1232
1680
1386
Continuous (at 460/480 V) [A]
730
780
780
890
890
1050
1050
1160
Intermittent (60 s overload) (at
460/480 V) [A]
1095
858
1170
979
1335
1155
1575
1276
Continuous kVA (at 400 V) [kVA]
554
610
610
686
686
776
776
873
Continuous kVA (at 460 V) [kVA]
582
621
621
709
709
837
837
924
Continuous kVA (at 480 V) [kVA]
632
675
675
771
771
909
909
1005
Max. Input current
Continuous (at 400 V) [A]
779
857
857
964
964
1090
1090
1227
Continuous (at 460/480 V) [A]
711
759
759
867
867
1022
1022
1129
Max. pre-fuses
1)
[A]
1600
2000
Max. cable size
Motor (mm
2
/AWG
2)
)
8 x 150 (8 x 300 mcm)
Line power (mm
2
/AWG
2
)
8 x 240 (8 x 500 mcm)
Brake (mm
2
/AWG
2)
)
4 x 185 (4 x 350 mcm)
Total LHD loss 400 V AC [kW]
20077
21909
21851
24592
23320
26640
26559
30519
Total backchannel loss 400 V AC
[kW]
16242
17767
17714
19984
18965
21728
21654
24936
Total filter loss 400 V AC [kW]
11047
11747
11705
12771
12670
14128
14068
15845
Total LHD loss 460 V AC [kW]
18855
19896
19842
22353
21260
25030
25015
27989
Total backchannel loss 460 V AC
[kW]
15260
16131
16083
18175
17286
20428
20417
22897
Total filter loss 460 V AC [kW]
10643
11020
10983
11929
11846
13435
13434
14776
Weight, enclosure IP21, IP54
(lbs [kg])
2009
Efficiency
4)
0.96
Output frequency [Hz]
0–600
Heatsink overtemp. trip (°F [°C])
221 [105]
Power card ambient trip (°F [°C])
185 [85]
*High overload = 160% torque during 60 s; Normal overload = 110% torque during 60 s
Table 11.3 Line Power Supply 3x380–480 V AC
1) For type of fuse, see
.
2) American wire gauge.
3) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.
Specifications
Instruction Manual
MG37A222
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
151
11
11
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......