11.5.3 Supplementary Fuses - High Power
Supplementary fuses
Frame size
Bussmann PN
Rating
D, E and F
KTK-4
4 A, 600 V
Table 11.12 SMPS Fuse
Size/Type
Bussmann PN
Littelfuse
Rating
P132–P250, 380–500 V
KTK-4
4 A, 600 V
P315–P630, 380–500 V
KLK-15
15 A, 600 V
Table 11.13 Fan Fuses
Size/Type
Bussmann PN
Rating
Alternative Fuses
P450–P630, 380–500 V
2.5–4.0 A
LPJ-6 SP or SPI
6 A, 600 V
Any listed class J dual
element, time delay, 6A
P450–P630, 380–500 V
4.0–6.3 A
LPJ-10 SP or SPI
10 A, 600 V
Any listed class J dual
element, time delay, 10 A
P450–P630, 380–500 V
6.3–10 A
LPJ-15 SP or SPI
15 A, 600 V
Any listed class J dual
element, time delay, 15 A
P450–P630, 380–500 V
10–16 A
LPJ-25 SP or SPI
25 A, 600 V
Any listed class J dual
element, time delay, 25 A
Table 11.14 Manual Motor Controller Fuses
Frame size
Bussmann PN*
Rating
Alternative Fuses
F
LPJ-30 SP or SPI
30 A, 600 V
Any listed Class J dual element, time delay, 30 A
Table 11.15 30 A Fuse Protected Terminal Fuse
Frame size
Bussmann PN*
Rating
Alternative Fuses
F
LPJ-6 SP or SPI
6 A, 600 V
Any listed class J dual element, time delay, 6 A
Table 11.16 Control Transformer Fuse
Frame size
Bussmann PN*
Rating
F
GMC-800MA
800 mA, 250 V
Table 11.17 NAMUR Fuse
Frame size
Bussmann PN*
Rating
Alternative Fuses
F
LP-CC-6
6 A, 600 V
Any listed class CC, 6 A
Table 11.18 Safety Relay Coil Fuse with PILS Relay
Frame size
Littelfuse PN
Rating
D, E, F
KLK-15
15 A, 600 V
Table 11.19 Electrical Fuses (Power Card)
Specifications
Instruction Manual
166
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
11
11
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......