4.3 Overview of Enclosures, 380–500 V
Enclosure size
D1h
D2h
D3h
D4h
D5h
D6h
D7h
D8h
Power rating
1)
Output at 400 V (kW)
90–132
160–250
90–132
160–250
90–132
90–132
160–250
160–250
Output at 460 V (hp)
125–200
250–350
125–200
250–350
125–200
125–200
250–350
250–350
Protection rating
IP
IP21/54
IP21/54
IP20
IP20
IP21/54
IP21/54
IP21/54
IP21/54
NEMA
Type 1/12
Type 1/12
Type Chassis Type Chassis
Type 1/12
Type 1/12
Type 1/12
Type 1/12
Hardware options
2)
Stainless steel back
channel
O
O
O
O
O
O
O
O
Mains shielding
O
O
–
–
O
O
O
O
Space heater
O
O
–
–
O
O
O
O
RFI filter (Class A1)
O
O
O
O
O
O
O
O
Safe torque off
S
S
S
S
S
S
S
S
No LCP
O
O
O
O
O
O
O
O
Numerical LCP
O
O
O
O
O
O
O
O
Graphical LCP
O
O
O
O
O
O
O
O
Fuses
O
O
O
O
O
O
O
O
Heat sink access
3)
O
O
O
O
O
O
O
O
Brake chopper
–
–
O
O
O
O
O
O
Regeneration terminals
–
–
O
O
O
O
O
O
Loadshare terminals
–
–
O
O
–
–
–
–
Fuses + loadshare
–
–
O
O
–
–
–
–
Disconnect
–
–
–
–
–
O
–
O
Circuit breakers
–
–
–
–
–
O
–
O
Contactors
–
–
–
–
–
O
–
O
24 V DC supply
O
O
O
O
O
O
O
O
Dimensions
Height, mm (in)
901 (35.5)
1107 (43.6)
909 (35.8)
1004 (39.5)
4)
1027 (40.4)
1027 (40.4)
4)
1324 (52.1)
1663 (65.5)
1978 (77.9)
2284 (89.9)
Width, mm (in)
325 (12.8)
325 (12.8)
250 (9.8)
375 (14.8)
325 (12.8)
325 (12.8)
420 (16.5)
420 (16.5)
Depth, mm (in)
379 (14.9)
379 (14.9)
375 (14.8)
375 (14.8)
381 (15.0)
381 (15.0)
386 (15.2)
406 (16.0)
Weight, kg (lb)
62 (137)
125 (276)
62 (137)
108 (238)
4)
125 (276)
179 (395)
4)
99 (218)
128 (282)
185 (408)
232 (512)
Table 4.3 D1h–D8h Drives, 380–500 V
1) All power ratings are taken at high overload. Output is measured at 400 V (kW) and 460 V (hp).
2) S = standard, O = optional, and a dash indicates that the option is unavailable.
3) Heat sink access is not available with stainless steel back-channel option.
4) With optional load share and regen terminals.
Product Overview
VLT® AutomationDrive FC 302
12
Danfoss A/S © 01/2018 All rights reserved.
MG38C202
4
4