Motor cable length, m (ft)
dv/dt (kV/
µs)
0
100
(328)
200
(656)
1.00
2.00
3.00
4.00
5.00
6.00
300
(984)
e30bu008.10
1
2
3
4
1
Unshielded cable with no filter
2
Shielded cable with no filter
3
Unshielded cable with dU/dt filter
4
Shielded cable with dU/dt filter
Illustration 10.21 dU/dt at Motor Terminals for Enclosures E2h/
E4h, 525–690 V
Motor cable length, m (ft)
V
pp
/V
line
0
100
(328)
200
(656)
0.50
1.50
2.00
3.00
3.50
4.00
300
(984)
e30bu009.10
2.50
1.00
1
2
3
4
1
Unshielded cable with dU/dt filter
2
Shielded cable with dU/dt filter
3
Shielded cable with no filter
4
Unshielded cable with no filter
Illustration 10.22 Peak Voltages at Motor Terminals for
Enclosures E2h/E4h, 525–690 V
Motor cable length, m (ft)
dv/dt (kV/
µs)
0
100
(328)
200
(656)
0.50
1.00
1.50
2.00
2.50
300
(984)
e30bu010.10
1
2
3
4
1
Shielded cable with no filter
2
Unshielded cable with no filter
3
Unshielded cable with dU/dt filter
4
Shielded cable with dU/dt filter
Illustration 10.23 Peak Voltages at Motor Terminals for
Enclosures E2h/E4h, 525–690 V
Motor cable length, m (ft)
V
pp
/V
line
0
100
(328)
200
(656)
0.50
1.50
2.00
3.00
3.50
4.00
300
(984)
e30bu011.10
2.50
1.00
1
2
3
4
1
Unshielded cable with dU/dt filter
2
Shielded cable with dU/dt filter
3
Shielded cable with no filter
4
Unshielded cable with no filter
Illustration 10.24 Peak Voltages at Motor Terminals for
Enclosures E2h/E4h, 525–690 V