7 Specifications
7.1 Electrical Data, 380–500 V
VLT
®
AutomationDrive FC 302
N90K
N110
N132
High/normal overload
HO
NO
HO
NO
HO
NO
(High overload=150% current during 60 s, normal
overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
90
110
110
132
132
160
Typical shaft output at 460 V [hp]
125
150
150
200
200
250
Typical shaft output at 500 V [kW]
110
132
132
160
160
200
Enclosure size
D1h/D3h/D5h/D6h
Output current (3-phase)
Continuous (at 400 V) [A]
177
212
212
260
260
315
Intermittent (60 s overload) (at 400 V)[A]
266
233
318
286
390
347
Continuous (at 460/500 V) [A]
160
190
190
240
240
302
Intermittent (60 s overload) (at 460/500 V) [kVA]
240
209
285
264
360
332
Continuous kVA (at 400 V) [kVA]
123
147
147
180
180
218
Continuous kVA (at 460 V) [kVA]
127
151
151
191
191
241
Continuous kVA (at 500 V) [kVA]
139
165
165
208
208
262
Maximum input current
Continuous (at 400 V) [A]
171
204
204
251
251
304
Continuous (at 460/500 V) [A]
154
183
183
231
231
291
Maximum number and size of cables per phase
- Mains, motor, brake, and load share [mm
2
(AWG)]
2x95 (2x3/0)
2x95 (2x3/0)
2x95 (2x3/0)
Maximum external mains fuses [A]
1)
315
350
400
Estimated power loss at 400 V [W]
2), 3)
2031
2559
2289
2954
2923
3770
Estimated power loss at 460 V [W]
2), 3)
1828
2261
2051
2724
2089
3628
Efficiency
3)
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [
°
C (
°
F)]
75 (167)
75 (167)
75 (167)
Table 7.1 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x380–500 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
Specifications
VLT® AutomationDrive FC 302
36
Danfoss A/S © 01/2018 All rights reserved.
MG38C202
7
7