VLT
®
AutomationDrive FC 302
N315
N355
N400
High/normal overload
HO
NO
HO
NO
HO
NO
(High overload=150% current during 60 s,
normal overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
315
355
355
400
400
450
Typical shaft output at 460 V [hp]
450
500
500
600
550
600
Typical shaft output at 500 V [kW]
355
400
400
500
500
530
Enclosure size
E1h/E3h
E1h/E3h
E1h/E3h
Output current (3-phase)
Continuous (at 400 V) [A]
600
658
658
745
695
800
Intermittent (60 s overload) (at 400 V) [A]
900
724
987
820
1043
880
Continuous (at 460/500 V) [A]
540
590
590
678
678
730
Intermittent (60 s overload) (at 460/500 V) [A]
810
649
885
746
1017
803
Continuous kVA (at 400 V) [kVA]
416
456
456
516
482
554
Continuous kVA (at 460 V) [kVA]
430
470
470
540
540
582
Continuous kVA (at 500 V) [kVA]
468
511
511
587
587
632
Maximum input current
Continuous (at 400 V) [A]
578
634
634
718
670
771
Continuous (at 460/500 V) [A]
520
569
569
653
653
704
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
2
(AWG)]
5x240 (5x500 mcm)
5x240 (5x500 mcm)
5x240 (5x500 mcm)
- Mains and motor with brake [mm
2
(AWG)]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
- Brake or regen [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Maximum number and size of cables per phase (E3h)
- Mains and motor [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Brake [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
- Load share or regen [mm
2
(AWG)]
4x185 (4x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
Maximum external mains fuses [A]
1)
800
800
800
Estimated power loss at 400 V [W]
2), 3)
6178
6928
6851
8036
7297
8783
Estimated power loss at 460 V [W]
2), 3)
5322
5910
5846
6933
7240
7969
Efficiency
3)
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [
°
C (
°
F)]
80 (176)
80 (176)
80 (176)
Power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
Fan power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
Active in-rush card overtemperature trip [
°
C
(
°
F)]
85 (185)
85 (185)
85 (185)
Table 7.3 Electrical Data for Enclosures E1h/E3h, Mains Supply 3x380–500 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
Specifications
VLT® AutomationDrive FC 302
38
Danfoss A/S © 01/2018 All rights reserved.
MG38C202