VLT
®
AutomationDrive FC 302
N160
N200
N250
N315
High/normal overload
HO
NO
HO
NO
HO
NO
HO
NO
(High overload=150% current during 60 s,
normal overload=110% current during 60 s)
Typical Shaft output at 525 V [kW]
132
160
160
200
200
250
250
315
Typical Shaft output at 575 V [hp]
200
250
250
300
300
350
350
400
Typical Shaft output at 690 V [kW]
160
200
200
250
250
315
315
400
Enclosure size
D2h/D4h/D7h/D8h
Output current (3-phase)
Continuous (at 525 V) [A]
201
253
253
303
303
360
360
418
Intermittent (60 s overload) (at 525 V)[A]
301
278
380
333
455
396
540
460
Continuous (at 575/690 V) [A]
192
242
242
290
290
344
344
400
Intermittent (60 s overload) (at 575/690 V) [A]
288
266
363
319
435
378
516
440
Continuous kVA (at 525 V) [kVA]
183
230
230
276
276
327
327
380
Continuous kVA (at 575 V) [kVA]
191
241
241
289
289
343
343
398
Continuous kVA (at 575/690 V) [kVA]
229
289
289
347
347
411
411
478
Maximum input current
Continuous (at 525 V) [A]
193
244
244
292
292
347
347
403
Continuous (at 575/690 V)
185
233
233
279
279
332
332
385
Maximum number and size of cables per phase
- Mains, motor, brake, and load share
[mm
2
(AWG)]
2x185 (2x350)
2x185 (2x350)
2x185 (2x350)
2x185 (2x350)
Maximum external mains fuses [A]
1)
550
550
550
550
Estimated power loss at 575 V [W]
2), 3)
2361
3074
3012
3723
3642
4465
4146
5028
Estimated power loss at 690 V [W]
2), 3)
2446
3175
3123
3851
3771
4614
4258
5155
Efficiency
3)
0.98
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [
°
C (
°
F)]
80 (176)
80 (176)
80 (176)
80 (176)
Table 7.6 Electrical Data for Enclosures D2h/D4h/D7h/D8h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.