7.3 Mains Supply
Mains supply (L1, L2, L3)
Supply voltage
380–500 V ±10%, 525–690 V ±10%
Mains voltage low/mains voltage drop-out:
During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop
level, which corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be
expected at mains voltage lower than 10% below the lowest rated supply voltage of the drive.
Supply frequency
50/60 Hz ±5%
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
1)
True power factor (λ)
≥0.9 nominal at rated load
Displacement power factor (cos Φ) near unity
(>0.98)
Switching on input supply L1, L2, L3 (power ups)
Maximum 1 time/2 minute
Environment according to EN60664-1
Overvoltage category III/pollution degree 2
The drive is suitable for use on a circuit capable of delivering up to 100 kA short circuit current rating (SCCR) at 480/600 V.
1) Calculations based on UL/IEC61800-3.
7.4 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–590 Hz
1)
Output frequency in flux mode
0–300 Hz
Switching on output
Unlimited
Ramp times
0.01–3600 s
1) Dependent on voltage and power.
Torque characteristics
Starting torque (constant torque)
Maximum 150% for 60 s
1), 2)
Overload torque (constant torque)
Maximum 150% for 60 s
1), 2)
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
7.5 Ambient Conditions
Environment
D1h/D2h/D5h/D6h/D7h/D8h/E1h/E2h enclosure
IP21/Type 1, IP54/Type 12
D3h/D4h/E3h/E4h enclosure
IP20/Chassis
Vibration test (standard/ruggedized)
0.7 g/1.0 g
Relative humidity
5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
Aggressive environment (IEC 60068-2-43) H
2
S test
Class Kd
Aggressive gases (IEC 60721-3-3)
Class 3C3
Test method according to IEC 60068-2-43
H2S (10 days)
Ambient temperature (at SFAVM switching mode)
- with derating
Maximum 55
°
C (131
°
F)
1)
- with full output power of typical EFF2 motors (up to 90% output current)
Maximum 50
°
C (122
°
F)
1)
- at full continuous FC output current
Maximum 45
°
C (113
°
F)
1)
Minimum ambient temperature during full-scale operation
0
°
C (32
°
F)
Minimum ambient temperature at reduced performance
-10
°
C (14
°
F)
Temperature during storage/transport
-25 to +65/70
°
C (13 to 149/158
°
F)
Maximum altitude above sea level without derating
1000 m (3281 ft)
Maximum altitude above sea level with derating
3000 m (9842 ft)
1) For more information on derating, see chapter 9.6 Derating.