8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates the set-up selection via the fieldbus/
serial communication port, and via 1 of the
digital inputs.
[3]
*
Logic OR
Activates the set-up selection via the fieldbus/
serial communication port, or via 1 of the
digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
fieldbus.
[0]
Digital
input
Activates preset reference selection via a digital
input.
[1]
Bus
Activates preset reference selection via the
serial communication port or fieldbus option.
[2]
Logic AND Activates preset reference selection via the
fieldbus/serial communication port, and via 1 of
the digital inputs.
[3]
*
Logic OR
Activates the preset reference selection via the
fieldbus/serial communication port, or via 1 of
the digital inputs.
8-90 Bus Jog 1 Speed
Range:
Function:
100 RPM
*
[ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
8-91 Bus Jog 2 Speed
Range:
Function:
200 RPM
*
[ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
10-00 CAN Protocol
Option:
Function:
NOTICE
The options depend on installed option.
[0] CANopen
[1] DeviceNet View the active CAN protocol.
10-01 Baud Rate Select
Select the fieldbus transmission speed. The selection must
correspond to the transmission speed of the master and the
other fieldbus nodes.
Option:
Function:
[16]
10 Kbps
[17]
20 Kbps
[18]
50 Kbps
[19]
100 Kbps
[20]
125 Kbps
[21]
250 Kbps
[22]
500 Kbps
10-02 MAC ID
Range:
Function:
Size related
*
[ 0 - 127] Selection of station address. Every
station connected to the same network
must have an unambiguous address.
10-05 Readout Transmit Error Counter
Range:
Function:
0
*
[0 - 255 ] View the number of CAN control transmission
errors since the last power-up.
10-06 Readout Receive Error Counter
Range:
Function:
0
*
[0 - 255 ] View the number of CAN control receipt errors
since the last power-up.
10-33 Store Always
Option: Function:
[0]
*
Off Deactivates non-volatile storage of data.
[1]
On Stores parameter data received via VLT
®
DeviceNet
MCA 104 in EEPROM non-volatile memory as default.
10-50 Process Data Config. Write
Only elements [2] and [3] of this array can be selected ([0] and
[1] are fixed).
Option:
Function:
[0]
*
None
[1]
16-80 Fieldbus CTW 1
[2]
16-82 Fieldbus REF 1
[3]
3-02 Minimum Reference
[4]
3-03 Maximum Reference
[5]
3-12 Catch Up/Slow Down Value
[6]
3-41 Ramp 1 Ramp Up Time
[7]
3-42 Ramp 1 Ramp Down Time
[8]
3-51 Ramp 2 Ramp Up Time
[9]
3-52 Ramp 2 Ramp Down Time
[10]
3-80 Jog Ramp Time
[11]
3-81 Quick Stop RampTime
[12]
4-11 Motor Speed Low Limit (RPM)
[13]
4-13 Motor Speed High Limit (RPM)
Parameters
Programming Guide
MG92G102