5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
[41]
Below
reference, low
The reference is lower than the
limit set in
[42]
Above ref,
high
The reference is higher than the
limit set in
.
[44]
Oil boost
active
[45]
Bus Control
The output is configured in
parameter 5-90 Digital & Relay Bus
Control
[60]
Comparator 0
See
parameter group 13-1*
Comparators
. If Comparator 0 is
evaluated as TRUE, the output goes
high. Otherwise, it is low.
[61]
Comparator 1
See
parameter group 13-1*
Comparators
. If Comparator 2 is
evaluated as TRUE, the output goes
high. Otherwise, it is low.
[62]
Comparator 2
See
parameter group 13-1*
Comparators
. If Comparator 2 is
evaluated as TRUE, the output goes
high. Otherwise, it is low.
[63]
Comparator 3
See
parameter group 13-1*
Comparators
. If Comparator 3 is
evaluated as TRUE, the output goes
high. Otherwise, it is low.
[64]
Comparator 4
See
parameter group 13-1*
Comparators
. If Comparator 4 is
evaluated as TRUE, the output goes
high. Otherwise, it is low.
[65]
Comparator 5
See
parameter group 13-1*
Comparators
. If Comparator 5 is
evaluated as TRUE, the output goes
high. Otherwise, it is low.
[70]
Logic rule 0
See
parameter group 13-4* Logic
Rules
. If Logic rule 0 is evaluated as
TRUE, the output goes high.
Otherwise, it is low.
[71]
Logic rule 1
See
parameter group 13-4* Logic
Rules
. If Logic rule 1 is evaluated as
TRUE, the output goes high.
Otherwise, it is low.
[72]
Logic rule 2
See
parameter group 13-4* Logic
Rules
. If Logic rule 2 is evaluated as
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
TRUE, the output goes high.
Otherwise, it is low.
[73]
Logic rule 3
See
parameter group 13-4* Logic
Rules
. If Logic rule 3 is evaluated as
TRUE, the output goes high.
Otherwise, it is low.
[74]
Logic rule 4
See
parameter group 13-4* Logic
Rules
. If Logic rule 4 is evaluated as
TRUE, the output goes high.
Otherwise, it is low.
[75]
Logic rule 5
See
parameter group 13-4* Logic
Rules
. If Logic rule 5 is evaluated as
TRUE, the output goes high.
Otherwise, it is low.
[80]
SL digital
output A
See
. The input goes high
whenever the smart logic action
[38] Set dig. out. A high
is executed.
The input goes low whenever the
smart logic
[32] Action Set dig. out.
A low is executed.
[81]
SL digital
output B
See
. The input goes high
whenever the smart logic action
[39] Set dig. out. B high
is executed.
The input goes low whenever the
smart logic
[33] Action Set dig. out. B
low
is executed.
[82]
SL digital
output C
See
. The input goes high
whenever the smart logic action
[40] Set dig. out. C high
is executed.
The input goes low whenever the
smart logic
[34] Action Set dig. out. C
low
is executed.
[83]
SL digital
output D
See
. The input goes high
whenever the smart logic
[41]
Action Set dig. out. D
high is
executed. The input goes low
whenever the smart logic
[35]
Action Set dig. out. D low
is
executed.
[160]
No alarm
The output is high when no alarm
is present.
[161]
Running
reverse
The output is high when the
frequency converter runs counter-
Parameters
Programming Guide
MG18P202
Danfoss A/S © 06/2019 All rights reserved.
33
3
3