Ref./Feedback
[RPM]
Analog input
High Ref./
Feedb. Value'
Low Ref./
Feedb. Value'
'Low Voltage'or
'Low Current'
'High Voltage'or
'High Current'
130BA038.13
1 V
5 V
10 V
300
600
900
1200
1500
[V]
150
Par 6-xx
Par 6-xx
Par 6-xx
Par 6-xx
Illustration 3.8 Live Zero Timeout Function
3.7.2 6-1* Analog Input 53
Parameters for configuring the scaling and limits for analog
input 53 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V
*
[0 - 10 V]
Enter the voltage (V) that
corresponds to
parameter 6-14 Terminal 53 Low Ref./
Feedb. Value
. To activate
parameter 6-01 Live Zero Timeout
Function
, set the value to >1 V.
6-11 Terminal 53 High Voltage
Range:
Function:
10 V
*
[0 - 10 V]
Enter the voltage (V) that
corresponds to the high reference
value (set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value
6-12 Terminal 53 Low Current
Range:
Function:
4 mA
*
[0 - 20 mA]
Enter the low current value. This
reference signal corresponds to the
low reference/ feedback value that
is set in
. To activate
parameter 6-01 Live Zero Timeout
Function
, set the value to >2 mA.
6-13 Terminal 53 High Current
Range:
Function:
20 mA
*
[0 - 20 mA]
Enter the high current value
corresponding to the high
reference/feedback set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value
.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
Size
related
*
[-4999 -
4999 ]
Enter the reference or feedback
value that corresponds to the
voltage or current set in
parameter 6-10 Terminal 53 Low
Voltage
to
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
200
*
[-4999 -
4999 ]
Enter the reference or feedback
value that corresponds to the
voltage or current set in
parameter 6-11 Terminal 53 High
Voltage
to
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.01 s
*
[0.01 - 10 s]
Enter the time constant. This
constant is a first-order digital low-
pass filter time constant for
suppressing electrical noise in
terminal 53. A high time constant
value improves dampening, but
also increases the time delay
through the filter.
6-19 Terminal 53 mode
Select whether terminal 53 is used for current or voltage input.
Option:
Function:
[0]
Current mode
[1]
*
Voltage mode
3.7.3 6-2* Analog Input 54
Parameters for configuring the scaling and limits for analog
input 54 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[0 - 10 V]
Enter the voltage (V) that
corresponds to the low reference
value (set in
parameter 6-24 Terminal 54 Low Ref./
Feedb. Value
). To activate
Parameters
VLT
®
Compressor Drive CDS 803
36
Danfoss A/S © 06/2019 All rights reserved.
MG18P202
3