6-74 Terminal 45 Output Max Scale
Scale for the maximum output (20 mA) of the analog signal at
terminal 45.
Range:
Function:
100 %
*
[0 - 200 %]
Set the value to be the percentage
of the full range of the variable
selected in
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-73
Variable
for
output
example:
Power
Analogue
Output
Max Scale
par. 6-74
Illustration 3.9 Output Maximum
Scale
6-76 Terminal 45 Output Bus Control
Range:
Function:
0
*
[0 - 16384 ]
Holds the level of analog output if
controlled by bus.
3.7.5 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital
output terminal 42. Analog outputs are current outputs:
0/4–20 mA. Resolution on analog outputs is 12 bit. Analog
output terminals can also be set up as digital output.
6-90 Terminal 42 Mode
Set terminal 42 to act as analog output or as digital output.
Option:
Function:
[0]
*
0-20 mA
[1]
4-20 mA
[2]
Digital Output
6-91 Terminal 42 Analog Output
Select the function of terminal 42 as an analog current output.
See also
parameter 6-90 Terminal 42 Mode
.
Option:
Function:
[0]
*
No operation
[100]
Output
frequency
0–100 Hz
[101]
Reference
Min
Ref.
–Max
Ref.
[102]
Feedback
Min
FB
–Max
FB
[103]
Motor Current 0–I
max
[106]
Power
0–P
nom
6-91 Terminal 42 Analog Output
Select the function of terminal 42 as an analog current output.
See also
parameter 6-90 Terminal 42 Mode
.
Option:
Function:
[139]
Bus Control
0–100%
[254]
DC Link
Voltage
6-92 Terminal 42 Digital Output
Select the function of Terminal 42 as an analog current output.
See also
parameter 6-90 Terminal 42 Mode
. See
for description of the choices.
Option:
Function:
[0]
*
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/
remote control
[4]
Standby / no
warning
[5]
Drive running
[6]
Running / no
warning
[7]
Run in
range/no
warning
[8]
Run on ref/no
warning
[9]
Alarm
[10]
Alarm or
warning
[12]
Out of current
range
[13]
Below current,
low
[14]
Above current,
high
[16]
Below speed,
low
[17]
Above speed,
high
[19]
Below
feedback, low
[20]
Above
feedback, high
[21]
Thermal
warning
[22]
Ready, no
thermal
warning
[23]
Remote, ready,
no thermal
warning
[24]
Ready, Voltage
OK
Parameters
Programming Guide
MG18P202
Danfoss A/S © 06/2019 All rights reserved.
39