1 Items  Supplied

Depending on the ordering number, the following is supplied:

Installation box, small size with switch (175X0318)

For use with FCD 302-315.

Illustration 1.1 Installation Box, Small Size with Switch (175X0318)

Installation box, small size without switch (175X0329)

For use with FCD 302-315.

Illustration 1.2 Installation Box, Small Size without Switch

(175X0329)

The functionality and design of the installation box without
switch is identical to the installation box with switch.

Installation box, large size with switch (175X0320)

For use with FCD 322-335.

Illustration 1.3 Installation Box, Large Size with Switch (175X0320)

The dimensions of the boxes are:

Small size: 300 x 192 x 145 mm

Large size: 367 x 258 x 154 mm

There are 6 plugs on the side of the installation box. The plugs
have the same functionality for all 3 types.

NOTICE

See the VLT

®

 Decentral Drive FCD 300 Design Guide for

further information.

2 Safety Instructions

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. Failure to wait the specified time after power
has been removed before performing service or repair work,
could result in death or serious injury.

1.

Stop motor.

2.

Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.

3.

Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration
of waiting time is specified in 

Table 2.1

.

Voltage

[V]

Power Range

[kW]

Minimum waiting

time

(min)

3 x 400

0.55–7.5

4

3 x 400

11–22

15

High voltage can be present even when the warning LED indicator

lights are off.

Table 2.1 Discharge Time

Installation Instructions

VLT® Decentral Drive FCD 300
Installation Box (175X0318/0320/0329)

MI04F102 – Rev 2013-11-25