4.8 Factory Settings
PNU #
Parameterdescription
Factory setting
Changes dur-
ing operation
4-setup
Conv.
index
Data
type
001
Language
English
Yes
No
0
5
002
Local/remote operation
Remote-controlled
Yes
Yes
0
5
003
Local reference
000,000.000
Yes
Yes
-3
4
004
Active Setup
Setup 1
Yes
No
0
5
005
Programming Setup
Active Setup
Yes
No
0
5
006
Setup copying
No copying
No
No
0
5
007
LCP copy
No copying
No
No
0
5
008
Display scaling
1.00
Yes
Yes
-2
6
009
Large display readout
Frequency [Hz]
Yes
Yes
0
5
010
Small display line 1.1
Reference [%]
Yes
Yes
0
5
011
Small display line 1.2
Motor current [A]
Yes
Yes
0
5
012
Small display line 1.3
Power [kW]
Yes
Yes
0
5
013
Local control
Remote control
as par. 100
Yes
Yes
0
5
014
Local stop/reset
Active
Yes
Yes
0
5
015
Local jog
Not active
Yes
Yes
0
5
016
Local reversing
Not active
Yes
Yes
0
5
017
Local reset of trip
Active
Yes
Yes
0
5
018
Data change lock
Not locked
Yes
Yes
0
5
019
Operating status at
power up
Forced stop,
use saved ref.
Yes
Yes
0
5
020
Lock for Hand mode
Active
Yes
No
0
5
024
User-defined Quick Menu
Not active
Yes
No
0
5
025
Quick Menu Setup
000
Yes
No
0
6
026
LED Status
Overload
Yes
Yes
0
5
4-Setup:
'Yes' means that the parameter can be programmed individually in each of the four Setups, i.e. one single parameter can have four different data values.
No' means that the data value will be the same in all Setups.
Conversion index:
This number refers to a conversion figure to be used when writing or
reading via serial communication with a frequency converter.
See also
Serial communication.
Conversion table
Conversion
index
Conversion
factor
73
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
-5
0.00001
Data type
:
Data type shows the type and length of the telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
VLT® Decentral FCD
4 All about FCD 300
MG.04.B8.02 - VLT is a registered Danfoss trademark
101
4