3.1.10 Manual Initialisation
NB!
Manual initialisation is not possible on the LCP 2
175N0131 control unit. It is, however, possible to per-
form an initialisation via par. 620
Operation mode
:
The following parameters are not changed when initialising via par. 620
Operation mode
.
-
par. 500
Address
-
par. 501
Baud rate
-
par. 600
Operating hours
-
par. 601
Hours run
-
par. 602
kWh counter
-
par. 603
Number of power-ups
-
par. 604
Number of overtemperatures
-
par. 605
Number of overvoltages
-
par. 615-617
Fault log
-
par. 678
Configure Control Card
3.2 Parameter Group 0-** Operation & Display
001
Language
Value:
English (english)
[0]
German (deutsch)
[1]
French (francais)
[2]
Danish (dansk)
[3]
Spanish (espanol)
[4]
Italian (italiano)
[5]
Function:
This parameter is used to choose the language to be shown in the display
whenever the LCP control unit is connected.
Description of choice:
There is a choice of the languages shown. The factory setting may vary.
002
Value:
Remote operation (REMOTE)
[0]
Local operation (LOCAL)
[1]
Function:
There is a choice of two different modes of operation of the adjustable
frequency drive;
Remote operation
[0] or
Local operation
[1]. See also
parameter 013
Local control
if
Local operation
[1] is selected.
Description of choice:
If
Remote operation
[0] is selected, the adjustable frequency drive is
controlled via:
1.
the control terminals or via serial communication.
2.
the [START] key. This cannot, however, override stop com-
mands transmitted via the digital inputs or via serial communi-
cation.
3.
the [STOP/RESET] and [JOG] keys, on the condition that these
are active.
If
Local operation
[1], is selected, the adjustable frequency drive is con-
trolled via:
1.
the [START] key. This cannot, however, override stop com-
mands via the digital inputs (see parameter 013
Local control
).
2.
the [STOP/RESET] and [JOG] keys, on the condition that these
are active.
3.
the [FWD/REV] key, on the condition that is has been selected
as active in parameter 016
Local reversing
, and that parameter
013
Local control
is set at
Local control and open loop
[1] or
Local control as parameter 100
[3]. Parameter 200
Output fre-
quency range
is set at
Both directions
.
4.
parameter 003
Local reference
where the reference can be set
using the [+] and [-] keys.
5.
an external control command that can be connected to the dig-
ital inputs (see parameter 013
Local control
).
NB!
The [JOG] and [FWD/REV] keys are located on the LCP
control unit.
003
Local reference
Value:
Par. 013
Local control
must be set to [1] or [2]:
0 - f
MAX
(par. 205)
50 Hz
Par. 013
Local control
must be set to [3] or [4].
Ref
MIN
- Ref
MAX
(par. 204-205)
0,0
Function:
In this parameter, the local reference can be set manually. The unit of
the local reference depends on the configuration selected in parameter
100
Configuration
.
Description of choice:
In order to protect the local reference, parameter 002
Local/remote op-
eration
must be set to
Local operation
[1]. Local reference cannot be set
via serial communication.
3 Programming
VLT® Decentral FCD
36
MG.04.B8.02 - VLT is a registered Danfoss trademark
3