3.2.1 Setup Configuration
There is a choice of four Setups (parameter Setups), which can be pro-
grammed independently of one another. The active Setup can be selected
in parameter 004
Active Setup
. When an LCP control unit is connected,
the active Setup number will be appear in the display under “Setup”. It
is also possible to preset the frequency converter to
Multisetup
, so that
it is possible to shift Setups using the digital inputs or serial communica-
tion. Setup shift can be used in a plant in which, for example, one Setup
is used for daytime operation and another one at night time.In parameter
006
Setup copying
it is possible to copy from one Setup to another. Using
parameter 007
LCP copy
all Setups can be transferred from one frequency
converter to another by moving the LCP control panel. First all parameter
values are copied to the LCP control panel, which can then be moved to
another frequency converter. Here all parameter values can be copied
from the LCP control unit to the frequency converter.
3.2.2 Setup Shift
-
Selection of Setup via terminals 29 and 33.
Par. 305
Digital input
=
Selection of Setup, lsb
[31]
Par. 307
Digital input
=
Selection of Setup, msb
[32]
Par. 004
Active setup
=
Multi Setup
[5]
004
Active Setup
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (setup 1)
[1]
Setup 2 (setup 2)
[2]
Setup 3 (setup 3)
[3]
Setup 4 (setup 4)
[4]
Multi Setup (MULTI SETUP)
[5]
Function:
The active parameter Setup is selected here. All parameters can be pro-
grammed in four individual parameter Setups. Shifts between Setups can
be made in this parameter via a digital input or via serial communication.
Description of choice:
Factory Setup
[0] contains the factory-set parameter values.
Setup 1-4
[1]-[4] are four individual Setups which can be selected as required.
Multi
Setup
[5] is used where remote-controlled shifts between the four Set-
ups via a digital input or via serial communication is required.
005
Programming Setup
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (setup 1)
[1]
Setup 2 (setup 2)
[2]
Setup 3 (setup 3)
[3]
Setup 4 (setup 4)
[4]
Active Setup (ACTIVE SETUP)
[5]
Function:
You can select which Setup you want to programme during operation
(applies both via the control panel and the serial communication port). It
is, for example, possible to programme
Setup 2
[2], while the active
Setup is set to
Setup 1
[1] in parameter 004
Active Setup
.
Description of choice:
Factory Setup
[0] contains the factory-set data and can be used as a
source of data if the other Setups are to be reset to a known status.
Setup
1-4
[1]-[4] are individual Setups that can be programmed freely during
operation. If
Active Setup
[5] is selected, the programming Setup will be
equal to parameter 004
Active Setup
.
NB!
If data is modified or copied to the active Setup, the
modifications have an immediate effect on the unit's
operation.
006
Setup copying
Value:
No copying (NO COPY)
[0]
Copy to Setup 1 from #
(COPY TO SETUP 1)
[1]
Copy to Setup 2 from #
(COPY TO SETUP 2)
[2]
Copy to Setup 3 from #
(COPY TO SETUP 3)
[3]
Copy to Setup 4 from #
(COPY TO SETUP 4)
[4]
Copy to all Setups from # (copy to all)
[5]
Function:
You can copy from the selected active Setup in parameter 005
Program-
ming setup
to the selected Setup or Setups in this parameter.
NB!
Copying is only possible in Stop (motor stopped in con-
nection with a stop command).
Description of choice:
Copying begins when the required copying function has been selected
and the [OK]/[CHANGE DATA] key has been pushed. The display indi-
cates when copying is in progress.
VLT® Decentral FCD
3 Programming
MG.04.B8.02 - VLT is a registered Danfoss trademark
37
3