6.2 Electrical Data
Enclosure
MH1
MH2
MH3
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
Overload
1)
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
Typical shaft
output [kW]
0.55
0.75
1.1
1.5
2.2
3.0
4.0
Typical shaft
output [hp]
0.75
1.0
1.5
2.0
3.0
4.0
5.0
Max. cable cross-
section in
terminals
2
(mains, motor)
[mm
2
/AWG]
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Output current
40
°
C ambient temperature
Continuous
(3x380-440 V) [A]
1.7
2.2
3.0
3.7
5.3
7.2
9.0
Intermittent
(3x380-440 V) [A]
1.9
2.7
2.4
3.5
3.3
4.8
4.1
5.9
5.8
8.5
7.9
11.5
9.9
14.4
Continuous
(3x440-480 V) [A]
1.6
2.1
2.8
3.4
4.8
6.3
8.2
Intermittent
(3x440-480 V) [A]
1.8
2.6
2.3
3.4
3.1
4.5
3.7
5.4
5.3
7.7
6.9
10.1
9.0
13.2
Max. input current
Continuous
(3x380-440 V )[A]
1.3
2.1
2.4
3.5
4.7
6.3
8.3
Intermittent
(3x380-440 V) [A]
1.4
2.0
2.3
2.6
2.6
3.7
3.9
4.6
5.2
7.0
6.9
9.6
9.1
12.0
Continuous
(3x440-480 V) [A]
1.2
1.8
2.2
2.9
3.9
5.3
6.8
Intermittent
(3 x 440-480 V)
[A]
1.3
1.9
2.0
2.5
2.4
3.5
3.2
4.2
4.3
6.3
5.8
8.4
7.5
11.0
Max. mains fuses
See
chapter 6.9 Fuse and Circuit Breaker Specifications
Table 6.11 Mains Supply 3x380-480 V AC Normal and High Overload: MH1, MH2, and MH3 Enclosure
1) NO: Normal overload, 110% for 1 minute. HO: High overload, 160% for 1 minute
A frequency converter intended for HO requires a corresponding motor rating. For example, Table 6.11 shows that a 1.5 kW motor for HO requires
a P2K2 frequency converter.
2) Max. cable cross-section is the largest cable cross-section that can be attached to the terminals. Always observe national and local regulations.
Specifications
VLT
®
DriveMotor FCP 106 and FCM 106 Design Guide
MG03M102 -
08/2015
53
6
6