Fault codes
Fault code
Frequency converter alarms
Fault descriptions
Communication Error
1
17
Loss of communication with the network
Over Current
2
59
Instantaneous output current has exceeded
frequency converter rated or programmed value
Over Temperature
3
69
Heat sink temperature limit has been reached
Over Speed Deviation
4
N.A.
N.A.
Over Voltage
5
7
DC link voltage has exceeded frequency converter
limit
Under Voltage
6
8
DC link voltage is lower than required frequency
converter limit
Short Circuit
7
16
Frequency converter output has shorted phase-to-
phase
Ground Fault
8
14
Frequency converter output grounding current has
exceeded manufacturer limitations
Motor Overload
9
10
Motor is overloaded
Inverter Overload
10
9
Timed over current fault
Over Torque Detection
11
N.A.
N.A.
External Fault
12
2, 24, 43, 60, 63,
External fault has been activated in the frequency
converter. This is a hard fault that must be reset.
Operator Interface Error
13
46, 47, 50, 51, 52, 53, 54, 55, 56,
57, 58
Inverter programming or operational interface
malfunction
Load Loss
14
93, 94, 95
Load on the Motor is less than programmed limit
of system. An Example is a broken belt or coupling
Configuration Error
15
40, 41
Errors exist in the programmed or operational
configuration of the inverter
Feedback Failure
16
N.A.
N.A.
Output Phase Loss
17
30, 31, 32
One or more of the output phases from the
inverter to the motor are open
Motor Stall
18
11
Motor is operating in stall region and not able to
accelerate
Power Unit Error
19
N.A.
N.A.
Input Phase/DC Ripple
20
4
Input single phase or low line voltage condition
Internal Drive Failure
21
38
Manufacturer defined internal operations that have
failed their-self checks.
Table 5.4 Mapping of Fault Codes
5.1.2 Binary Input and Output Objects
Object_Name
Present_Value
ID
Default name
Parameter
Bit number
BI:2
Digital input Term 29
1660
2
BI:3
Digital input Term 27
1660
3
BI:4
Digital input Term 19
1660
4
BI:5
Digital input Term 18
1660
5
BI:10..BI:15 are reserved for P1660/x
Table 5.5 Binary Inputs
ID
Object_Name
Present_Value
Default name
Parameter
Bit number
Writeable
Cmd.able
Timeout
BO:4
Relay 1
590
4
x
x
x
BO:5
Relay 2
590
5
x
x
x
Table 5.6 Binary Outputs
BACnet Objects
VLT
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
16
MG03O102 - Danfoss A/S
©