8-54 Reversing Select
Option:
Function:
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
[0]
*
Digital
input
Activates Reverse command via a digital input.
[1]
Bus
Activates Reverse command via the serial
communication port.
[2]
Logic
AND
Activates Reverse command via the serial
communication port, AND additionally via one of
the digital inputs.
[3]
Logic
OR
Activates Reverse command via the serial
communication port OR via one of the digital
inputs.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the serial communication port.
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
[0]
Digital
input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial
communication port.
[2]
Logic
AND
Activates the set-up selection via the serial
communication port, AND additionally via one of
the digital inputs.
[3]
*
Logic
OR
Activate the set-up selection via the serial
communication port OR via one of the digital
inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter Preset
Reference selection via the terminals (digital
input) and/or via the serial communication port.
[0]
Digital
input
Activates Preset Reference selection via a digital
input.
[1]
Bus
Activates Preset Reference selection via the
serial communication port.
[2]
Logic
AND
Activates Preset Reference selection via the
serial communication port, AND additionally via
one of the digital inputs.
8-56 Preset Reference Select
Option:
Function:
[3]
*
Logic OR
Activates the Preset Reference selection via the
serial communication port OR via one of the
digital inputs.
6.2.4 8-7* BACnet
8-70 BACnet Device Instance
Range:
Function:
1
*
[0 - 4194303 ] Enter a unique ID number for the BACnet
device.
8-72 MS/TP Max Masters
Range:
Function:
127
*
[0 - 127 ] Define the address of the master which holds
the highest address in this network. Decreasing
this value optimises polling for the token.
8-73 MS/TP Max Info Frames
Range:
Function:
1
*
[1 - 65534 ] Define how many info/data frames the device
is allowed to send while holding the token.
8-74 "I am" Service
Option:
Function:
[0]
*
Send at
power-up
Select when the device should send the “I-
Am” service message only at power-up.
[1]
Continuously
Select when the device should send the "I-
Am" service message continuously with an
interval of approx. 1 min.
8-75 Intialisation Password
Range:
Function:
admin
*
[1 - 1 ] Enter the password needed for execution of
Drive Re-initialisation.
8-79 Protocol Firmware version
Range:
Function:
Size related
*
[0 - 65535 ] Read the supported protocol version.
Index 5 is for BACNet.
6.2.5 8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus
communication via the FC Port.
8-80 Bus Message Count
Range:
Function:
0
*
[0 - 65536 ] This parameter shows the number of valid
telegrams detected on the bus.
Parameters
VLT
®
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
MG03O102 - Danfoss A/S
©
12/2013. All rights reserved.
23
6
6
Summary of Contents for VLT DriveMotor FCP 106
Page 2: ......