N75K
N90K
N110
N132
N160
N200
Normal Load*
NO
NO
NO
NO
NO
NO
Typical Shaft output at 550 V [kW]
55
75
90
110
132
160
Typical Shaft output at 575 V [hp]
75
100
125
150
200
250
Typical Shaft ouptut at 690 V [kW]
75
90
110
132
160
200
Enclosure IP21
D1h
D1h
D1h
D1h
D1h
D2h
Enclosure IP54
D1h
D1h
D1h
D1h
D1h
D2h
Enclosure IP20
D3h
D3h
D3h
D3h
D3h
D4h
Output current
Continuous (at 550 V) [A]
90
113
137
162
201
253
Intermittent (60 s overload) (at 550
V) [A]
99
124
151
178
221
278
Continuous (at 575/690 V) [A]
86
108
131
155
192
242
Intermittent (60 s overload) (at
575/690 V) [kVA]
95
119
144
171
211
266
Continuous kVA (at 550 V) [kVA]
86
108
131
154
191
241
Continuous kVA (at 575 V) [kVA]
86
108
130
154
191
241
Continuous kVA (at 690 V) [kVA]
103
129
157
185
229
289
Max. Input current
Continuous (at 550 V) [A]
89
110
130
158
198
245
Continuous (at 575 V) [A]
85
106
124
151
189
234
Continuous (at 690 V) [A]
87
109
128
155
197
240
Max. cable size: line power, motor,
brake and load share [mm (AWG)]
2x95 (2x3/0)
2x185
(2x350 mcm)
Max. external electrical fuses [A]
160
315
315
315
350
350
Estimated power loss at 575 V [hp,
W]
1.557, 1161
1.912, 1426
2.332, 1739
2.815, 2099
3.548, 2646
4.118, 3071
Estimated power loss at 690 V [hp,
W]
1.613, 1203
1.979, 1476
2.408, 1796
2.903, 2165
3.672, 2738
4.254, 3172
Weight, enclosure IP21, IP54 kg
(lbs)
62 (135)
125 (275)
Weight, enclosure IP20 kg (lbs)
62 (135)
125 (275)
Efficiency
0.98
Output frequency
0–590 Hz
Heatsink overtemp. trip
230° F [110°C]
Power card ambient trip
167° F [75°C]
*Normal overload=110% current for 60 s
Table 10.2 Line Power Supply 3x525–690 V AC
Specifications
VLT
®
HVAC Drive D-Frame
Instruction Manual
10-2
MG16D222 - VLT
®
is a registered Danfoss trademark
10
10