background image

VLT

® 

MCA 121 EtherNet/IP Add On Instruction 

MIxxxxxx - VLT

® 

is a registered Danfoss trademark 

 

 

 

 

 

5.

 

Verify

 

that

 

the

 

following

 

screen

 

does

 

not

 

contain

 

any

 

warnings

 

or

 

errors.

 

This

 

is

 

done

 

by

 

selecting

 

the

 

“Error/Warnings”

 

icon

 

in

 

the

 

Import

 

content

 

windows.

 

 

 

 

 

 

 

 

 

 

 

If warnings and/or errors exist, the Add-On Instruction will not work properly. If no Errors/Warnings are present, then 
the Add-On Instruction can be imported by pressing the “OK” Button. No further settings are required in this menu. 

6.

 

Verify the Add-On Instruction is available under the “Add-On Instruction” menu and looks similar to Figure 4. And that 
the name is the same. 

 

 

 

 

Figure 3

 

Figure 4

Summary of Contents for VLT FC Series

Page 1: ...MAKING MODERN LIVING POSSIBLE Instruction VLT FC Series Add On Instruction for MCA 121 EtherNet IP...

Page 2: ...the end user For an example program open the provided sample program EthIP acd Note that when using this version of the AOI version 20 0 or later of RSLogix 5000 Earlier versions of RSLogix do not su...

Page 3: ...ource 3 Option A A connection between terminal 12 13 and terminal 27 is required if parameter 8 01 is set to 0 Digital and ctrl word 4 The default setting of the drive allows the drive to continue ope...

Page 4: ...the following parameters via the Main Menu Parameter Description Setting 12 21 0 Process Data Config Write 1680 Fieldbus CTW 1 12 21 1 1682 Fieldbus REF 1 12 22 0 Process Data Config Read 1603 Status...

Page 5: ...2 Import the Add On Instruction by selecting Add On Instruction in the navigation tree and press the right mouse button and select Import Add On Instruction Figure 1 Import Add On Instruction 3 Select...

Page 6: ...in the Import content windows If warnings and or errors exist the Add On Instruction will not work properly If no Errors Warnings are present then the Add On Instruction can be imported by pressing t...

Page 7: ...e following module dialog will appear as in figure 5 1 Insert the IP address used in Par 12 01 e g 192 168 1 10 All IP addresses must unique for each device connected to the network 2 Set the Name fie...

Page 8: ...Add On Instruction 5 0 Setting up the Add On Instruction The Danfoss Add On Instruction can be copied to the PLC s rung This is done by opening the Add On Instruction folder and drag and drop the VLT...

Page 9: ...tions Reset Boolean In transition from 0 to 1 a fault trip can be reset MRV Real Main Reference Value Speed set point in of nominal motor speed The function of the output tags are Name Type Descriptio...

Page 10: ...the actual drive e g FC302 I1 Data New tags can be created by right clicking in the desired field and selecting New tag The same procedure must be done with the DriveOut field in order to control the...

Page 11: ...www danfoss com drives 130R0xyz MIyyuxxxx Rev 2013 09 20...

Reviews: