8.11.4.2 Bit 01, Drive Ready
Bit 01=0: The drive is not ready.
Bit 01=1: The drive is ready for operation, but the coasting command is active via the digital inputs or via serial communication.
8.11.4.3 Bit 02, Coast Stop
Bit 02=0: The drive releases the motor.
Bit 02=1: The drive starts the motor with a start command.
8.11.4.4 Bit 03, No Error/Trip
Bit 03=0: The drive is not in fault mode.
Bit 03=1: The drive trips. To re-establish operation, press [Reset].
8.11.4.5 Bit 04, No Error/Error (No Trip)
Bit 04=0: The drive is not in fault mode.
Bit 04=1: The drive shows an error but does not trip.
8.11.4.6 Bit 05, Not Used
Bit 05 is not used in the status word.
8.11.4.7 Bit 06, No Error/Triplock
Bit 06=0: The drive is not in fault mode.
Bit 06=1: The drive is tripped and locked.
8.11.4.8 Bit 07, No Warning/Warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
8.11.4.9 Bit 08, Speed ≠ Reference/Speed=Reference
Bit 08=0: The motor runs, but the present speed is different from the preset speed reference. It might happen when the speed
ramps up/down during start/stop.
Bit 08=1: The motor speed matches the preset speed reference.
8.11.4.10 Bit 09, Local Operation/Bus Control
Bit 09=0: [Off/Reset] is activated on the control unit or
[2] Local
in
parameter 3-13 Reference Site
is selected. It is not possible to con-
trol the drive via serial communication.
Bit 09=1: It is possible to control the drive via the fieldbus/serial communication.
8.11.4.11 Bit 10, Out of Frequency Limit
Bit 10=0: The output frequency has reached the value in
parameter 4-12 Motor Speed Low Limit [Hz]
or
parameter 4-14 Motor Speed
High Limit [Hz]
.
Bit 10=1: The output frequency is within the defined limits.
8.11.4.12 Bit 11, No Operation/In Operation
Bit 11=0: The motor is not running.
Bit 11=1: The drive has a start signal or the output frequency is greater than 0 Hz.
8.11.4.13 Bit 12, Drive OK/Stopped, Auto Start
Bit 12=0: There is no temporary overtemperature on the drive.
Bit 12=1: The drive stops because of overtemperature but the unit does not trip and resumes operation once the overtemperature
normalizes.
8.11.4.14 Bit 13, Voltage OK/Limit Exceeded
Bit 13=0: There are no voltage warnings.
AJ363928382091en-000101 / 130R0983 | 129
Danfoss A/S © 2021.04
RS485 Installation and Set-up
VLT® Flow Drive FC 111
Design Guide