Cable length [m (ft)]
AC line voltage [V]
Rise time [μsec]
V
peak
[kV]
dU/dt [kV/μsec]
50 (164)
400
0.222
1.00
3.603
400 V 30 kW (40 hp)
10 (33)
400
0.376
0.92
1.957
50 (164)
400
0.536
0.97
1.448
100 (328)
400
0.696
0.95
1.092
150 (492)
400
0.8
0.965
0.965
10 (33)
480
0.384
1.2
2.5
50 (164)
480
0.632
1.18
1.494
100 (328)
480
0.712
1.2
1.348
150 (492)
480
0.832
1.17
1.125
10 (33)
500
0.408
1.24
2.431
50 (164)
500
0.592
1.29
1.743
100 (328)
500
0.656
1.28
1.561
150 (492)
500
0.84
1.26
1.2
400 V 37 kW (50 hp)
10 (33)
400
0.276
0.928
2.69
50 (164)
400
0.432
1.02
1.889
10 (33)
480
0.272
1.17
3.441
50 (164)
480
0.384
1.21
2.521
10 (33)
500
0.288
1.2
3.333
50 (164)
500
0.384
1.27
2.646
400 V 45 kW (60 hp)
10 (33)
400
0.3
0.936
2.496
50 (164)
400
0.44
0.924
1.68
100 (328)
400
0.56
0.92
1.314
150 (492)
400
0.8
0.92
0.92
10 (33)
480
0.3
1.19
3.173
50 (164)
480
0.4
1.15
2.3
100 (328)
480
0.48
1.14
1.9
150 (492)
480
0.72
1.14
1.267
10 (33)
500
0.3
1.22
3.253
50 (164)
500
0.38
1.2
2.526
100 (328)
500
0.56
1.16
1.657
150 (492)
500
0.74
1.16
1.254
400 V 55 kW (74 hp)
10 (33)
400
0.46
1.12
1.948
AJ363928382091en-000101 / 130R0983 | 79
Danfoss A/S © 2021.04
Electrical Installation
Considerations
VLT® Flow Drive FC 111
Design Guide