5 Mechanical Installation Considerations
5.1 Power Ratings, Weights, and Dimensions
e
f
a
e
e
f
a
d
e
A
a
b
B
C
D
e
3
0
b
f9
8
4
.1
0
Illustration 40: Dimensions, Enclosure Sizes H1–H8
Table 31: Power Ratings, Weights, and Dimensions, Enclosure Sizes H1–H4
Enclosure Size
H1
H2
H3
H4
IP class
IP20
IP20
IP20
IP20
Power [kW (hp)]
3x380–480 V
0.37–1.5
(0.5–2.0)
2.2–4.0
(3.0–5.0)
5.5–7.5
(7.5–10)
11–15
(15–20)
Height [mm (in)]
A
195 (7.7)
227 (8.9)
255 (10.0)
296 (11.7)
A
(1)
273 (10.7)
303 (11.9)
329 (13.0)
359 (14.1)
a
183 (7.2)
212 (8.3)
240 (9.4)
275 (10.8)
Width [mm (in)]
B
75 (3.0)
90 (3.5)
100 (3.9)
135 (5.3)
b
56 (2.2)
65 (2.6)
74 (2.9)
105 (4.1)
Depth [mm (in)]
C
168 (6.6)
190 (7.5)
206 (8.1)
241 (9.5)
Mounting hole [mm (in)]
d
9 (0.35)
11 (0.43)
11 (0.43)
12.6 (0.50)
e
4.5 (0.18)
5.5 (0.22)
5.5 (0.22)
7 (0.28)
f
5.3 (0.21)
7.4 (0.29)
8.1 (0.32)
8.4 (0.33)
Maximum weight kg (lb)
2.1 (4.6)
3.4 (7.5)
4.5 (9.9)
7.9 (17.4)
1
Including decoupling plate.
Table 32: Power Ratings, Weights, and Dimensions H6–H8
Enclosure Size
H5
H6
H7
H8
IP class
IP20
IP20
IP20
IP20
Power [kW (hp)]
3x380–480 V
18.5–22
(25–30)
30–45
(40–60)
55–75
(70–100)
90 (125)
Height [mm (in)]
A
334 (13.1)
518 (20.4)
550 (21.7)
660 (26)
A
(1)
402 (15.8)
595 (23.4)/635 (25), 45 kW
630 (24.8)/690 (27.2), 75 kW
800 (31.5)
AJ363928382091en-000101 / 130R0983 | 53
Danfoss A/S © 2021.04
Mechanical Installation
Considerations
VLT® Flow Drive FC 111
Design Guide