7.4 Readout and Programming of Indexed Parameters
Procedure
Select the parameter and press [OK].
Press [
▵
]/[
▿
] to scroll through the indexed values.
To change the parameter value, select the indexed value and press [OK].
Change the value by pressing [
▵
]/[
▿
].
Press [OK] or [Cancel] to accept or abort the new setting.
Press [Back] to leave the parameter.
7.5 Initialization to Default Settings
There are 2 ways to initialize the drive to the default settings.
Recommended initialization
Two-finger initialization
Initialization of parameters is confirmed by
alarm 80, Drive initialised
in the display after the power cycle.
7.5.1 Recommended Initialization
Procedure
Select
parameter 14-22 Operation Mode
.
Press [OK].
Select
[2] Initialisation
and press [OK].
Power off the drive and wait until the display turns off.
Reconnect the mains supply. The drive is now reset, except for the following parameters.
Parameter 1-06 Clockwise Direction
Parameter 8-30 Protocol
Parameter 8-31 Address
Parameter 8-32 Baud Rate
Parameter 8-33 Parity / Stop Bits
Parameter 8-35 Minimum Response Delay
Parameter 8-36 Maximum Response Delay
Parameter 8-37 Maximum Inter-char delay
Parameter 8-70 BACnet Device Instance
Parameter 8-72 MS/TP Max Masters
Parameter 8-73 MS/TP Max Info Frames
Parameter 8-74 "I am" Service
Parameter 8-75 Intialisation Password
Parameter 15-00 Operating hours
to
parameter 15-05 Over Volt's
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter 15-30 Alarm Log: Error Code
Parameter group 15-4* Drive identification
Parameter 18-10 FireMode Log:Event
7.5.2 Two-finger Initialization
Procedure
Power off the drive.
AJ363928382091en-000101 / 130R0983 | 99