3.5.5 Semi-Automatic Bypass Speed Set-up
The Semi-Automatic Bypass Speed Set-up can be used to
facilitate the programming of the frequencies to be
skipped due to resonances in the system.
The following process is to be carried out:
1.
Stop the motor.
NOTE!
Smaller adjustable frequency drives have a ramp time of
three seconds which can make it difficult to set the bypass
speeds. Adjust the ramp times in
and
2.
Select
[1] Enabled
in
3.
Press [Hand On] to start the search for frequency
bands causing resonances. The motor will ramp
up according to the ramp set.
NOTE!
Terminal 27 Digital Input
5-12 Terminal 27 Digital Input
has
coast inverse as default setting. This means that [Hand On]
will not start the motor if there is no 24 V to terminal 27,
so connect terminal 12 to terminal 27.
4.
When sweeping through a resonance band, press
[OK] on the LCP when leaving the band. The
actual frequency will be stored as the first
element in
(array).
Repeat this for each resonance band identified at
the ramp-up (maximum three can be adjusted).
5.
When maximum speed has been reached, the
motor will automatically begin to ramp down.
Repeat the above procedure when speed is
leaving the resonance bands during the
deceleration. The actual frequencies registered
when pressing [OK] will be stored in
6.
When the motor has ramped down to stop, press
[OK]. The
will
automatically reset to Off. The adjustable
frequency drive will stay in
Hand On
mode until
[Off] or [Auto On] is pressed.
If the frequencies for a certain resonance band are not
registered in the right order (frequency values stored in
By
Pass Speed To
are higher than those in
By Pass Speed From
)
or if they do not have the same numbers of registrations
for the
By Pass From
and
By Pass To
, all registrations will be
canceled and the following message is displayed:
Collected
speed areas overlapping or not completely determined. Press
[Cancel] to abort
.
4-64 Semi-Auto Bypass Set-up
Option:
Function:
[0]
Off
[1]
Enable
Parameters
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
3-19
3
3