13-02 Stop Event
Option:
Function:
[28] Logic rule 2
Use the result of logic rule 2 in the
logic rule.
[29] Logic rule 3
Use the result of logic rule 3 in the
logic rule.
[30] SL Time-out 0
Use the result of timer 0 in the logic
rule.
[31] SL Time-out 1
Use the result of timer 1 in the logic
rule.
[32] SL Time-out 2
Use the result of timer 2 in the logic
rule.
[33] Digital input DI18
Use the value of DI18 in the logic rule
(High = TRUE).
[34] Digital input DI19
[35] Digital input DI27
Use the value of DI27 in the logic rule
(High = TRUE).
[36] Digital input DI29
Use the value of DI29 in the logic rule
(High = TRUE).
[39] Start command
This event is TRUE if the adjustable
frequency drive is started by any means
(either via digital input, serial communi-
cation bus or other).
[40] Drive stopped
This event is TRUE if the adjustable
frequency drive is stopped or coasted
by any means (either via digital input,
serial communication bus or other).
[42] Auto Reset Trip
This event is TRUE if the adjustable
frequency drive is tripped (but not trip-
locked) and an automatic reset is
issued.
[50] Comparator 4
Use the result of comparator 4 in the
logic rule.
[51] Comparator 5
Use the result of comparator 5 in the
logic rule.
[60] Logic rule 4
Use the result of logic rule 4 in the
logic rule.
[61] Logic rule 5
Use the result of logic rule 5 in the
logic rule.
[70] SL Time-out 3
Use the result of timer 3 in the logic
rule.
[71] SL Time-out 4
Use the result of timer 4 in the logic
rule.
[72] SL Time-out 5
Use the result of timer 5 in the logic
rule.
[73] SL Time-out 6
Use the result of timer 6 in the logic
rule.
13-02 Stop Event
Option:
Function:
[74] SL Time-out 7
Use the result of timer 7 in the logic
rule.
[83] Broken Belt
A broken belt condition has been
detected. This function must be
enabled in
13-03 Reset SLC
Option:
Function:
[0] Do not reset
SLC
Retains programmed settings in all group
13 parameters (13-*).
[1] Reset SLC
Resets all group 13 parameters (13-*) to
default settings.
3.9.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e., output frequency, output current, analog input, etc.)
to fixed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Figure 3.14
In addition, there are digital values that will be compared
to fixed time values. See explanation in
. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to program Comparator 0,
select index 1 to program Comparator 1, etc.
13-10 Comparator Operand
Array [6]
Option:
Function:
Select the variable to be monitored by
the comparator.
[0]
Disabled
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor Current
[6]
Motor power
Parameters
VLT
®
HVAC Basic Drive Programming Guide
3-42
MG18B222 - VLT
®