0-12 Link Setups
Option:
Function:
[20] Linked
Copies “not changeable during operation”
parameters from one set-up to the other, so they
are identical in both set-ups.
3.1.3 0-3* LCP Custom Readout
It is possible to customize the display elements for various
purposes: *Custom Readout. Value proportional to speed
(linear, squared or cubed depending on unit selected in
) *Display Text. Text string stored
in a parameter.
Custom Readout
The calculated value to be displayed is based on settings
in
,
(linear only),
4-14 Motor Speed High Limit [Hz]
and actual speed.
0
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
Liniar
units only
P 0-31
Motor Speed
130BB779.10
Motor Speed
High limit
P 4-14 (Hz)
Linear Unit (e
.g. Speed and flo
w)
Quadr
atic Unit (P
ressur
e)
Cubic Unit (P
ow
er)
Figure 3.1
The relation will depend on the type of unit selected in
:
Unit Type
Speed Relation
Dimensionless
Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Quadratic
Power
Cubic
Table 3.1
0-30 Custom Readout Unit
Option:
Function:
Program a value to be shown in the
display of the LCP. The value has a linear,
squared or cubed relation to speed. This
relation depends on the unit selected (see
table above). The actual calculated value
can be read in
.
[0]
None
[1]
%
[5]
PPM
[10]
l/Min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m3/s
[24]
m3/min
[25]
m3/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
Degree Celsius
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m Wg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
Parameters
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
3-3