13-52 SL Controller Action
Array [20]
Option:
Function:
[34]
Set digital out C
low
Any output with digital output 3 selected
is low (off).
[35]
Set digital out
D low
Any output with digital output 4 selected
is low (off).
[36]
Set digital out E
low
Any output with digital output 5 selected
is low (off).
[37]
Set digital out F
low
Any output with digital output 6 selected
is low (off).
[38]
Set digital out
A high
Any output with digital output 1 selected
is high (closed).
[39]
Set digital out B
high
Any output with digital output 2 selected
is high (closed).
[40]
Set digital out C
high
Any output with digital output 3 selected
is high (closed).
[41]
Set digital out
D high
Any output with digital output 4 selected
is high (closed).
[42]
Set digital out E
high
Any output with digital output 5 selected
is high (closed).
[43]
Set digital out F
high
Any output with digital output 6 selected
is high (closed).
[60]
Reset Counter A Resets counter A to zero.
[61]
Reset Counter B Resets counter B to zero.
[62]
Counter A (up)
[63]
Counter A
(down)
[64]
Counter B (up)
[65]
Counter B
(down)
[70]
Start Timer 3
Starts timer 3, see
for further description.
[71]
Start Timer 4
Starts timer 4, see
for further description.
[72]
Start Timer 5
Starts timer 5, see
for further description.
[73]
Start Timer 6
Starts timer 6, see
for further description.
[74]
Start Timer 7
Starts timer 7, see
for further description.
[80]
Sleep Mode
Starts the sleep mode.
[90]
Set ECB Bypass
Mode
[91]
Set ECB Drive
Mode
[100] Reset Alarms
Parameter Descriptions
Programming Guide