8a
Parameter 22-34 Low Speed Power [kW]
8b
Parameter 22-35 Low Speed Power [HP]
8c
Parameter 22-38 High Speed Power [kW]
.
8d
Parameter 22-39 High Speed Power [HP]
9.
Switch back with [Auto On] or [Off].
NOTICE
Set
parameter 1-03 Torque Characteristics
before tuning
takes place.
22-30 No-Flow Power
Range:
Function:
0 kW
*
[0 - 0 kW] Readout of calculated no-flow power at
actual speed. If power drops to the display
value, the frequency converter considers the
condition as a no-flow situation.
22-31 Power Correction Factor
Range:
Function:
100
%
*
[1 -
400 %]
Make corrections to the calculated power in
.
If no-flow is detected, when it should not be
detected, decrease the setting. However, if no-
flow is not detected, when it should be
detected, increase the setting to above 100%.
22-32 Low Speed [RPM]
Range:
Function:
Size
related
*
[ 0 - par.
22-36
RPM]
To be used if
has been set to
[0] RPM
(parameter
not visible if
[1] Hz
is selected).
Set used speed for the 50% level.
This function is used for storing values
needed to tune no-flow detection.
22-33 Low Speed [Hz]
Range:
Function:
Size
related
*
[ 0 - par.
22-37 Hz]
To be used if
has been set for
[1] Hz
(parameter
not visible if
[0] RPM
is selected).
Set used speed for the 50% level.
The function is used for storing values
needed to tune no-flow detection.
22-34 Low Speed Power [kW]
Range:
Function:
Size
related
*
[ 0 -
5.50
kW]
To be used if
has been set for
[0] International
(parameter not visible if
[1] North America
is
selected).
Set power consumption at 50% speed level.
This function is used for storing values
needed to tune no-flow detection.
22-35 Low Speed Power [HP]
Range:
Function:
Size
related
*
[ 0 -
7.50 hp]
To be used if
has been set for
[1] North America
(parameter not visible if
[0] International
is
selected).
Set power consumption at 50% speed level.
This function is used for storing values
needed to tune no-flow detection.
22-36 High Speed [RPM]
Range:
Function:
Size
related
*
[ 0 -
par. 4-13
RPM]
To be used if
has been set for
[0] RPM
(parameter
not visible if
[1] Hz
is selected).
Set used speed for the 85% level.
The function is used for storing values
needed to tune no-flow detection.
22-37 High Speed [Hz]
Range:
Function:
Size
related
*
[ 0 -
par. 4-14
Hz]
To be used if
has been set for
[1] Hz
(parameter not
visible if
[0] RPM
is selected).
Set used speed for the 85% level.
The function is used for storing values
needed to tune no-flow detection.
22-38 High Speed Power [kW]
Range:
Function:
Size
related
*
[ 0 -
5.50
kW]
To be used if
has been set for International
(parameter not visible if North America is
selected).
Set power consumption at 85% speed level.
This function is used for storing values
needed to tune no-flow detection.
22-39 High Speed Power [HP]
Range:
Function:
Size
related
*
[ 0 -
7.50 hp]
To be used if
has been set for North America
(parameter not visible if International is
selected).
Set power consumption at 85% speed level.
This function is used for storing values
needed to tune no-flow detection.
3.20.3 22-4* Sleep Mode
If the load on the system allows for stop of the motor and
the load is monitored, the motor can be stopped by
activating the sleep mode function. This is not a normal
stop command, but ramps the motor down to 0 RPM and
Parameter Descriptions
VLT
®
HVAC Drive FC 102
164