0-41 [Off] Key on LCP
Option:
Function:
[0]
Disabled Key disabled avoids accidental usage of the key.
[1]
*
Enabled
[Off] key is enabled.
[2]
Password Avoid unauthorised stop. If
is included in
My Personal Menu
,
define the password in
. Otherwise, define the password
in
parameter 0-60 Main Menu Password
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disabled Key disabled avoids accidental usage of the
[Auto On] key.
[1]
*
Enabled
[Auto On] key is enabled.
[2]
Password Avoid unauthorised start in Auto mode. If
parameter 0-42 [Auto on] Key on LCP
is included
in
My Personal Menu
, define the password in
parameter 0-65 Personal Menu Password
Otherwise, define the password in
parameter 0-60 Main Menu Password
.
0-43 [Reset] Key on LCP
Option:
Function:
[0]
Disabled
Key disabled avoids accidental usage of the
[Reset] key.
[1]
*
Enabled
[Reset] key is enabled.
[2]
Password
Avoid unauthorised resetting. If
parameter 0-43 [Reset] Key on LCP
is included
in
parameter 0-25 My Personal Menu
, define
the password in
. Otherwise, define the
password in
.
[3]
Enabled
without OFF
[4]
Password
without OFF
[5]
Enabled with
OFF
Pressing the key resets the frequency
converter, but does not start it.
[6]
Password
with OFF
Prevents unauthorised reset. Upon
authorised reset, the frequency converter
does not start. See option
[2] Password
for
information on how to set the password.
3.2.6 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from 1
frequency converter to another.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
No function.
[1]
All to LCP
Copies all parameters in all set-ups from the
frequency converter memory to the LCP
memory. For service purposes it is
recommended to copy all parameters to the
LCP after commissioning.
[2]
All from LCP Copies all parameters in all set-ups from the
LCP memory to the frequency converter
memory.
[3]
Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. The latest
selection can be used to programme several
frequency converters with the same function
without disturbing motor data which are
already set.
[10] Delete LCP
copy data
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function.
[1]
Copy to
set-up 1
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
) to set-up 1.
[2]
Copy to
set-up 2
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
) to set-up 2.
[3]
Copy to
set-up 3
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
) to set-up 3.
[4]
Copy to
set-up 4
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
) to set-up 4.
[9]
Copy to
all
Copies the parameters in the present set-up to
each of the set-ups 1 to 4.
3.2.7 0-6* Password
0-60 Main Menu Password
Range:
Function:
100
*
[-9999 -
9999 ]
Define the password for access to the Main
Menu via the [Main Menu] key. If
parameter 0-61 Access to Main Menu w/o
Password
is set to
[0] Full access
, this
parameter is ignored.