24-01 Fire Mode Configuration
Option:
Function:
NOTICE
Before adjusting the PID controller set
parameter 24-09 Fire Mode Alarm Handling
,
[2] Trip, All Alarms/Test
.
NOTICE
If
[2] Enable-Run Reverse
is selected in
parameter 24-00 Fire Mode Function
,
[3]
Closed Loop
cannot be selected in
parameter 24-01 Fire Mode Configuration
[0]
*
Open
Loop
When fire mode is active, the motor runs with a
fixed speed based on a reference set. The unit is
the same as selected in
.
[3]
Closed
Loop
When fire mode is active, the built-in PID
controller controls the speed based on the
setpoint and a feedback signal selected in
parameter 24-07 Fire Mode Feedback Source
. Select
the unit in
parameter 24-02 Fire Mode Unit
. For
other PID controller settings use parameter group
20-** FC Closed Loop
as for normal operation. If the
motor also is controlled by the built-in PID
controller when in normal operation, the same
transmitter can be used for both cases by
selecting the same source.
24-02 Fire Mode Unit
Option:
Function:
Select the desired unit when fire mode is active
and running in closed loop.
[0]
None
[1]
%
[2]
RPM
[3]
Hz
[4]
Nm
[5]
PPM
[10]
1/min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
24-02 Fire Mode Unit
Option:
Function:
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[75]
mm Hg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in²
[172] in WG
[173] ft WG
[174] in Hg
[180] HP
24-03 Fire Mode Min Reference
Range:
Function:
Size
related
*
[ -999999.999
- par. 24-04
FireModeUnit]
Minimum value for the reference/
setpoint (limiting the sum of value in
parameter 24-05 Fire Mode Preset
Reference
and value of signal on
input selected in
).
If running in open loop when fire
mode is active, the unit is selected by
the setting of
. For closed loop, select the
unit in
Parameter Descriptions
VLT
®
HVAC Drive FC 102
186