0-11 Programming Set-up
Option:
Function:
Select the set-up to be edited (that is
programmed) during operation; either the
active set-up or 1 of the inactive set-ups. The
set-up number being edited is displayed in the
LCP in brackets.
[0]
Factory
setup
Cannot be edited, but it is useful as a data
source to return the other set-ups to a known
state.
[1]
Set-up 1
[1] Set-up 1
to
[4] Set-up 4
can be edited freely
during operation, independently of the active
set-up.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
*
Active Set-
up
(I.e. the set-up in which the frequency
converter is operating) can also be edited
during operation. Editing parameters in the
selected set-up would normally be done from
the LCP, but it is also possible from any of the
serial communication ports.
0-12 This Set-up Linked to
Option:
Function:
This parameter only needs to be programmed if
changing set-ups is required while the motor is
running. It ensures that parameters which are
‘not changeable during operation’
have the same
setting in all relevant set-ups.
To enable conflict-free changes from 1 set-up to
another while the frequency converter is
running, link set-ups containing parameters
which are not changeable during operation.
The link ensures synchronising of the
not
changeable during operation
parameter values
when moving from 1 set-up to another during
operation.
Not changeable during operation
parameters can be identified by the label FALSE
in the parameter lists in
.
The
parameter 0-12 This Set-up Linked to
feature
is used when
[9] Multi set-up
in
is selected.
[9] Multi
set-up
can be used to move from 1 set-up to
another during operation while the motor runs.
xample:
Use
[9] Multi set-up
to shift from set-up 1 to set-
up 2 while the motor runs. Programme
parameters in set-up 1 first, then ensure that
set-up 1 and set-up 2 are synchronised (or
linked). Synchronisation can be performed in 2
ways:
0-12 This Set-up Linked to
Option:
Function:
•
Change the edit set-up to
[2] Set-up 2
in
parameter 0-11 Programming Set-up
and set
to
[1] Set-up 1
. This starts the
linking (synchronising) process.
130BP075.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[1]
Setup 1
Illustration 3.1 Set-up Handling
OR
•
While still in set-up 1, using
, copy set-up
1 to set-up 2. Then set
parameter 0-12 This Set-up Linked to
to
[2] Set-up 2
. This starts the linking
process.
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
Illustration 3.2 Set-up Handling
After the link is complete,
parameter 0-13 Readout: Linked Set-ups
reads
set-ups 1 and 2 to indicate that all
not
changeable during operation
parameters are now
the same in set-up 1 and set-up 2. If there are
changes to a
not changeable during operation
parameter, for example
, in set-up 2, they are also
changed automatically in set-up 1. A switch
between set-up 1 and set-up 2 during
operation is now possible.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
27