0-61 Access to Main Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in
parameter 0-60 Main Menu Password
[1]
LCP: Read only Prevents unauthorised editing of Main
Menu parameters.
[2]
LCP: No access Prevents unauthorised viewing and editing
of Main Menu parameters.
[3]
Bus: Read only
[4]
Bus: No access
[5]
All: Read only
[6]
All: No access
If
[0] Full access
is selected,
parameter 0-65 Personal Menu Password
, and
parameter 0-66 Access to Personal Menu w/o Password
are
ignored.
0-65 Personal Menu Password
Range:
Function:
200
*
[-9999 -
9999 ]
Define the password for access to My Personal
Menu via the [Quick Menu] key. If
parameter 0-66 Access to Personal Menu w/o
Password
is set to
[0] Full access
, this
parameter is ignored.
0-66 Access to Personal Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in
parameter 0-65 Personal Menu Password
.
[1]
LCP: Read only Prevents unauthorised editing of
My
Personal Menu
-parameters.
[2]
LCP: No access Prevents unauthorised viewing and editing
of
My Personal Menu
-parameters.
[3]
Bus: Read only
[4]
Bus: No access
[5]
All: Read only
[6]
All: No access
If
parameter 0-61 Access to Main Menu w/o Password
is set
to
[0] Full access
, this parameter is ignored.
0-67 Bus Password Access
Range:
Function:
0
*
[0 - 9999] Use this parameter to unlock the frequency
converter via fieldbus or MCT 10 Set-up Software.
3.2.8 0-7* Clock Settings
Set the time and date of the internal clock. The internal
clock can be used for for eaxmple timed actions, energy
log, trend analysis, date/time stamps on alarms, logged
data, and preventive maintenance.
It is possible to program the clock for daylight saving time/
summertime, weekly working days/non-working days
including 20 exceptions (holidays etc.). Although the clock
settings can be set via the LCP, they can also be set along
with timed actions and preventative maintenance
functions using the MCT 10 software tool.
NOTICE
The frequency converter has no back-up of the clock
function and the set date/time resets to default
(2000-01-01 00:00) after a power-down unless a real time
clock-module with back-up is installed. If no module with
back up is installed, only use the clock function if the
frequency converter is integrated into the BMS using
serial communications, with the BMS maintaining
synchronisation of control equipment clock times. In
it is possible to program for a
warning if in case the clock has not been set properly,
for example after a power down.
NOTICE
If mounting an analog I/O MCB 109 option card, a
battery back-up of the date and time is included.
0-70 Date and Time
Range:
Function:
Size
related
*
[ 0 - 0 ] Sets the date and time of the internal
clock. The format to be used is set in
and
.
0-71 Date Format
Option:
Function:
Sets the date format to be used in the LCP.
[0] YYYY-MM-DD
[1] DD-MM-YYYY
[2] MM/DD/YYYY
0-72 Time Format
Option:
Function:
Sets the time format to be used in the LCP.
[0]
24 h
[1]
12 h
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.