8-05 End-of-Timeout Function
Option:
Function:
•
[7] Set-up 1
.
•
[8] Set-up 2
.
•
[9] Set-up 3
.
•
[10] Set-up 4
.
[0]
Hold set-
up
Retains the set-up selected in
parameter 8-04 Control Timeout Function
and
displays a warning, until
toggles. Then the frequency
converter resumes its original set-up.
[1]
*
Resume
set-up
Resumes the set-up active before the time-out.
8-06 Reset Control Timeout
Option:
Function:
This parameter is active only when option
[0] Hold
set-up
has been selected in
[0]
*
Do not
reset
Retains the set-up specified in
parameter 8-04 Control Timeout Function
•
[7] Set-up 1
•
[8] Set-up 2
•
[9] Set-up 3
•
[10] Set-up 4
[1]
Do
reset
Returns the frequency converter to the original
set-up following a control word timeout. When the
value is set to
[1] Do reset
, the frequency converter
performs the reset and immediately reverts to the
[0] Do not reset
setting.
8-07 Diagnosis Trigger
Option:
Function:
Select
[0] Disable
to send no extended
diagnosis data (EDD). Select
[1] Trigger on
alarms
to send EDD upon alarms or
[2] Trigger
alarm/warn.
to send EDD upon alarms, or
warnings. Not all fieldbusses support the
diagnosis functions. This parameter has no
function for BACnet.
[0]
*
Disable
[1]
Trigger on
alarms
[2]
Trigger
alarm/warn.
8-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating,
this function is used. Select filtered, if the function is required. A
power cycle is required for changes to take effect.
Option:
Function:
[0]
Motor Data Std-
Filt.
Normal bus readouts.
[1]
Motor Data LP-
Filter
Filtered bus readouts of the
following parameters:
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage
16-14 Motor current
16-16 Torque [Nm]
16-17 Speed [RPM]
16-22 Torque [%]
16-25 Torque [Nm] High
3.9.2 8-1* Ctrl. Word Settings
8-10 Control Profile
Option:
Function:
Select the interpretation of the control
and status words corresponding to the
installed fieldbus. Only the selections valid
for the fieldbus installed in slot A are
visible in the LPC display.
[0]
*
FC profile
[1]
PROFIdrive
profile
[5]
ODVA
Available only with MCA 104 DeviceNet,
MCA 121 Ethernet/IP.
[7]
CANopen DSP
402
8-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of bits
12–15 in the status word.
[0]
No function
[1]
*
Profile Default Function corresponds to the profile default
selected in
parameter 8-10 Control Profile
[2]
Alarm 68
Only
Only set in case of an Alarm 68.
[3]
Trip excl.
Alarm 68
Set in case of a trip, except if Alarm 68
executes the trip.
[10] T18 DI status. The bit indicates the status of terminal 18.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[11] T19 DI status. The bit indicates the status of terminal 19.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[12] T27 DI status. The bit indicates the status of terminal 27.
0 indicates that the terminal is low.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
90
Danfoss A/S © 03/2015 All rights reserved.
MG11CE02
3