5.
6-11 Terminal 53 High Voltage
. Set maximum
external voltage reference on Terminal 53 at 10 V.
(This sets the maximum input signal at 10 V.)
Q3-21
130B
T765.10
6-11 Terminal 53 High
Voltage
10.00 V
14.7% 0.00A 1(1)
Analog Reference
Illustration 5.5
6.
6-14 Terminal 53 Low Ref./Feedb. Value
. Set
minimum speed reference on Terminal 53 at 6Hz.
(This tells the frequency converter that the
minimum voltage received on Terminal 53 (0 V)
equals 6 Hz output.)
130B
T773.11
Q3-21
14.7 % 0.00 A 1(1)
Analog Reference
6 - 14 Terminal 53 Low
Ref./Feedb. Value
000020.000
Illustration 5.6
7.
6-15 Terminal 53 High Ref./Feedb. Value
. Set
maximum speed reference on Terminal 53 at 60
Hz. (This tells the frequency converter that the
maximum voltage received on Terminal 53 (10V)
equals 60 Hz output.)
130B
T774.11
Q3-21
14.7 % 0.00 A 1(1)
Analog Reference
6 - 15 Terminal 53 High
Ref./Feedb. Value
50.000
Illustration 5.7
With an external device providing a 0-10 V control signal
connected to frequency converter terminal 53, the system
is now ready for operation. Note that the scroll bar on the
right in the last illustration of the display is at the bottom,
indicating the procedure is complete.
shows the wiring connections used to
enable this set up.
53
55
6-1*
+
A53
U - I
130BB482.10
0-10V
Illustration 5.8 Wiring Example for External Device Providing
0-10 V Control Signal (frequency converter left, external device
right)
5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
•
Each terminal has specified functions it is capable
of performing
•
Parameters associated with the terminal enable
the function
•
For proper frequency converter functioning, the
control terminals must be
Wired properly
Programmed for the intended function
Receiving a signal
See
for control terminal parameter number and
default setting. (Default setting can change based on the
selection in
0-03 Regional Settings
.)
The following example shows accessing Terminal 18 to see
the default setting.
1.
Press [Main Menu] twice, scroll to parameter
group 5-**
Digital In/Out Parameter Data Set
and
press [OK].
130B
T768.10
2-** Brakes
3-** Reference / Ramps
4-** Limits / Warnings
5-** Digital In/Out
14.6% 0.00A 1(1)
Main Menu
Illustration 5.9
About Frequency Converter P...
VLT
®
HVAC Drive Operating Instructions
MG11AH02 - VLT
®
is a registered Danfoss trademark
35
5
5