NOTE!
Any changes in par. 4-13
will reset the value in par. 4-53
4-14 Motor Speed High Limit [Hz]
Range:
Function:
Application
dependent*
[Application dependant]
NOTE!
Max. output frequency cannot exceed 10% of the inverter switching frequency (par. 14-01
4-53 Warning Speed High
Range:
Function:
Application
dependent*
[Application dependant]
NOTE!
Any changes in par. 4-13
will reset the value in par. 4-53
If a different value is needed in par. 4-53
, it must be set after programming of par. 4-13
4-56 Warning Feedback Low
Range:
Function:
-999999.99
9 Proc-
essCtrlU-
nit*
[Application dependant]
Enter the lower feedback limit. When the feedback falls below this limit, the display reads Feedb
Low. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02.
4-57 Warning Feedback High
Range:
Function:
999999.999
ProcessCtr-
lUnit*
[Application dependant]
Enter the upper feedback limit. When the feedback exceeds this limit, the display reads Feedb High.
The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02.
4-64 Semi-Auto Bypass Set-up
Option:
Function:
[0] *
OFF
No function
[1]
Enabled
Starts the semi-automatic bypass set-up and continue with the procedure described above.
VLT
®
HVAC Drive Instruction Manual
7 How to Program the Adjustable Frequency
Drive
MG.11.AB.22 - VLT
®
is a registered Danfoss trademark
7-23