Power Supply Module (PSM 510):
GSDML-V2.xx-Danfoss-PSM-yyyymmdd.xml
Decentral Access Module (DAM 510):
GSDML-V2.xx-Danfoss-DAM-2Port-IRT-yyyymmdd.xml
GSDML-V2.xx-Danfoss-DAM-3Port-RT-yyyymmdd.xml
GSDML-V2.xx-Danfoss-DAM-yyyymmdd.xml
Auxiliary Capacitors Module (ACM 510):
GSDML-V2.xx-Danfoss-ACM-yyyymmdd.xml
6.15.5 Creating a Network
Procedure
e3
0b
i2
55
.1
0
1
2
3
5
4
In the
Devices
window, select
Device configuration
[1] and add a PSM.
Assign the PSM to the PLC_1 by dragging the middle square under the PLC icon [2] onto the square at top left of the PSM
icon [3]. The PN/IE_1 network is created automatically.
Assign the PROFINET device name, IP address, and subnet mask to the PSM:
Right-click on the PSM icon.
Select the tab
General
.
Select
PROFINET interface [X1]
and then
Ethernet addresses
.
Enter the IP address 192.168.101.1 [4].
Enter the Subnet mask 255.255.255.0 [5].
Repeat steps 1–3 to add a DAM 510, ACM 510, ISD 510, or DSD 510.
In the
Devices & networks
window, select
Topology view
[1] and connect the devices by dragging and dropping the icons.
e3
0b
i2
56
.1
0
1
2
3 4
Remove any existing
MAIN [OB1]
operation block: