9.3.14 Brake Chopper Error
This fault applies to the PSM 510.
Possible causes
Faulty brake chopper.
Brake chopper power exceeds the power cycle limit.
Incorrect parameterization.
Troubleshooting
Check the parameterization of the brake chopper.
Check the brake chopper connection.
Measure the resistance of the brake chopper and compare it with the parameter settings.
9.3.15 Internal Fan Error
This fault applies to PSM 510.
Possible causes
Fan is not mounted.
Fan is blocked.
Troubleshooting
Check if the fan is blocked.
Check the fan cables for proper connection or damage.
9.4 Error Codes for ISD 511 Servo System
9.4.1 No error (0x0000 / 0x0)
This error code is valid for PSM 510, DAM 510, ACM 510, and ISD 511.
Table 27: No error (0x0000 / 0x0)
Code
PROFINET
®
code
Name
Severity (warning/error/trip lock)
Description
LCP name
0x0000
0x0
No error
Error
No error.
–
9.4.2 Generic application error (0x1000 / 0x100)
This error is valid for PSM 510, DAM 510, ACM 510, and ISD 511.
Table 28: Generic err (0x1000 / 0x100)
Code
PROFINET
®
code Name
Severity (warning/error/trip
lock)
Description
LCP name
0x1000 0x100
Generic application error Error
Generic application error. generic err
9.4.3 High cont. power overload (0x2313 / 0x161)
This error is valid for PSM 510.
Table 29: High cont. power overload (0x2313 / 0x161)
Code
PROFINET
®
code Name
Severity (warning/error/trip
lock)
Description
LCP name
0x2313 0x161
High cont. power
overload
Warning, error
High continuous power
overload error.
high pwr ovld
9.4.4 Continuous power overload (0x2314 / 0x162)
This error is valid for PSM 510.