Table 122: Pin Assignment of LCP Connector
Pins
Description
Notes
Rating/parameter
1
Not connected
–
–
2
/LCP RST
Reset
Active at
≦
0.5 V
3
LCP RS485
Positive RS485 signal
Speed:
38.4 kBd
The levels fulfill the RS485 specification.
4
/LCP RS485
Negative RS485 signal
5
GND
GND
–
6
VCC
5 V supply for LCP
5 V ±10% at 120 mA maximum load
N O T I C E
Only PELV potential can be connected to the LCP input.
11.6.7 AC Mains Connector
The AC mains connector is on the bottom of the Power Supply Module (PSM 510).
e30bg452.10
Illustration 83: AC Mains Connector
Table 123: Pin Assignment of AC Mains Connector
Pins
(left to
right)
Descrip-
tion
Notes
Rating/parameter
1
L3
Used to connect
L1/L2/L3
Nominal voltage: 400–480 V AC ±10%
Nominal power: 30 kW
Maximum cross-section: 16 mm
2
(AWG 4)
Conductor cross-section range 0.75–16 mm
2
, solid or flexible (AWG 18–AWG 4)
2
L2
3
L1
11.6.7.1 Mains Cable Cross-Sections for PSM 510
Table 124: Mains Cable Cross-Sections for PSM 510
PSM 510 (10 kW)
PSM 510 (20 kW)
PSM 510 (30 kW)
Minimum cable cross-section for CE
4 mm
2
(minimum 70 °C, Cu)
16 mm
2
(minimum 70 °C, Cu)
16 mm
2
(minimum 90 °C, Cu)
Minimum cable cross-section for UL
AWG 10
(minimum 60 °C, Cu)
AWG 6
(minimum 60 °C, Cu)
AWG 4
(minimum 75 °C, Cu)
11.6.8 Relay Connector
The relay connector is used for a user-defined reaction and is located as follows:
AQ377148425069en-000101
/ 130R1213
140 | Danfoss A/S © 2023.08
Specifications
VLT® Servo Drive System ISD 511
Operating Guide