Illustration 21: Connecting the PE Wire of the Feed-in Cable
1
PE screws on DAM 510
2
PE yellow/green wire (fork lug)
N O T I C E
The ISD 511 servo drive has 2 PE screws. The 2nd screw can be used to loop the earthing conductor for a maximum of 5 units.
If the system uses more than 5 units, ground them in groups of 5.
5.3.2 Grounding the System Modules
Do not ground the system modules in daisy-chain format. Use the grounding method shown in