5.2.14 Conversion of Parameter 121 Start Function
Table 41: Parameter 121
FCD 300 series
FCD 302 series
Parameter
121 Start Function
1-72 Start Function
Options
[0] DC Hold in Start Delay Time
[0] DC Hold/Delay Time
[1] DC Brake in Start Delay Time
[1] DC Brake/Delay Time
[2] Coasting in Start Delay Time
[2] Coast/Delay Time
[3] Start Frequency/Voltage Clockwise
[3] Start Speed CW
[4] Start Frequency/Voltage in Reference Direction
[4] Horizontal Operation
5.2.15 Conversion of Parameter 122 Function at Stop
Table 42: Parameter 122
FCD 300 series
FCD 302 series
Parameter
122 Function at Stop
1-80 Function at Stop
Options
[0] Coasting
[0] Coast
[1] DC Hold
[1] DC Hold
–
[2] Motor Check
–
[3] Pre-magnetizing
5.2.16 Conversion of Parameter 123 Min Frequency for Function at Stop
Table 43: Parameter 123
FCD 300 series
FCD 302 series
Parameter
123 Min Frequency for Function at Stop
1-82 Min Speed for Function at Stop [Hz]
Range
0.0–10.0 Hz
0.0–20.0 Hz
5.2.17 Conversion of Parameter 126 DC Braking Time
Table 44: Parameter 126
FCD 300 series
FCD 302 series
Parameter
126 DC Braking Time
2-02 DC Braking Time
Range
0.0–60.0 s
0.0–60.0 s
Parameter Mapping Lists
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
AQ289550754901en-000101 / 130R0890| 35