5.4.3 Conversion of Parameter 309 Terminal 53, Min. Scaling
Table 94: Parameter 309
FCD 300 series
FCD 302 series
Parameter
309 Terminal 53, Min. Scaling
6-10 Terminal 53 Low Voltage
Range
0–10.0 V
-10.00 to
parameter 6-11
5.4.4 Conversion of Parameter 310 Terminal 53, Max Scaling
Table 95: Parameter 310
FCD 300 series
FCD 302 series
Parameter
310 Terminal 53, Max Scaling
6-11 Terminal 53 High Voltage
Range
0–10.0 V
Parameter 6-10
to 10.00 V
5.4.5 Conversion of Parameter 314 Terminal 60, Analog Input Current
Table 96: Parameter 314
FCD 300 series
FCD 302 series
(1)
Parameter
314 Terminal 60, Analog Input Current
3-17 Reference Resource 3
7-00 Speed PID Feedback Source
1-93 Thermistor Resource
4-20 Torque Limit Factor Source
Options
[0] No Operation
Parameter 3-17 Reference Resource 3
set to
[0] No Function
[1] Reference
Parameter 3-17 Reference Resource 3
set to
[2] Analog Input 54
Parameter 7-00 Speed PID Source
set to
[7] Analog Input 54
[2] Feedback Signal
Parameter 7-00 Speed PID Feedback Source
set to
[7] Analog Input 54
[3] Torque Limit
Parameter 3-17 Reference Resource 3
set to
[2] Analog Input 54
Parameter 4-20 Torque Limit Factor Source
set to
[6] Analog Input 54
[10] Wobble
Not supported
1
The HW switch S202 for analog input 54 must be set to current (ON).
5.4.6 Conversion of Parameter 315 Terminal 60, Min. Scaling
Table 97: Parameter 315
FCD 300 series
FCD 302 series
Parameter
315 Terminal 60, Min. Scaling
6-22 Terminal 54 Low Current
Parameter Mapping Lists
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
AQ289550754901en-000101 / 130R0890
50 | Danfoss A/S © 2019.11