1.4.3 Performance
•
The VLT® Decentral Drive FCD 302 reacts faster on most commands as the VLT® Decentral Drive FCD 300/FCM 300, which can
influence the applications. When replacing a VLT® Decentral Drive FCD 300/FCM 300 with the VLT® FCD 300 PROFIBUS Converter
MCA 117, the installer must ensure that the functionality is maintained. Due to the different timing, it may be necessary to
reprogram the controller, where signals from the drives react faster.
•
The motor control algorithm of the VLT® Decentral Drive FCD 302 results in a better motor performance compared to FCD 300/FCM
300.
NOTICE
FACTORY SETTING OF PARAMETERS
After initialization of the FCD 302, most parameters are set to match the factory settings of the FCD 300/FCM 300 parameters.
NOTICE
LINKED SETUPS
To synchronize changes made with a running motor, ensure that setups are linked. Link the setups in
parameter 0-12 This Setup
Linked to
.
Introduction
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
AQ289550754901en-000101 / 130R0890| 7
Danfoss A/S © 2019.11